Operating instructions
88
THYRO-P (HF-TYPES) TYPE CURRENT AIR VOLUME SOUND PRESS.
50HZ 60HZ IN 1 m DIST.
I [A] I [A] [m
3
/h] [ca. dbA]
1P
200HF, 280HF 0.22 0.22 120 53
300HF, 495HF, 500HF, 650HF 0.50 0.38 150 67
780HF, 1000HF, 1400HF, 1500HF 0.55 0.60 580 75
2000HF, 2100HF, 2600HF, 2900HF 1.00 1.20 2200 81
2P / 1P...VSC 2
200HF, 280HF 0.50 0.38 200 67
300HF, 495HF, 500HF, 650HF 0.50 0.38 230 67
780HF, 1000HF, 1400HF, 1500HF 1.00 1.20 1200 81
1850HF, 2000HF, 2400HF, 2750HF 1.00 1.20 2100 81
3P / 1P...VSC 3
200HF, 280HF 0.50 0.38 260 67
300HF, 495HF, 500HF, 650HF 1.20 0.85 450 72
780HF, 1000HF, 1400HF, 1500HF 1.00 1.20 1600 81
1700HF, 1850HF, 2200HF, 2600HF 1.00 1.20 2000 81
Fans (for HF types) must be running when Thyro-P is operating. Connection according to connec-
ting diagrams in chapter 8.
When operating conditions are below +10°C, a longer start-up time of the fan has to be consi-
dered. Therefore the adjustable range should amount at least double of the specified continuous
current.
TABLE TERMINAL SCREWS THYRO-P 1P, 2P, 3P CONNECTOR EARTHING SCREW
U1, V1, W1, U2, V2, W2
37H, 75H M 6 M 6
80H M 8 M 10
110H M 6 M 6
130H, 170H M 8 M 10
200HF, 280HF, 300HF M 10 M 10
495HF, 500HF, 650HF
780HF, 1000HF, 1400HF, M 12 M 12
1500HF, 1700HF, 1850HF,
2000HF, 2100HF, 2200HF,
2400HF, 2600HF, 2750HF,
2900HF
WITH UL APPLICATIONS
POWER CONNECTION
USE ONLY 60°/75°C COPPER CONDUCTORS (UL SPECIFICATION)
STUD TORQUE FOR SCREW MIN RATED MAX
TABLE TERMINAL SCREWS M 2 0.2 0.25 0.3
[Nm] M 6 3.0 4.4 5.9
M 8 11.5 17.0 22.5
M 10 22.0 33.0 44
M 12 38.0 56.0 75
[Pound inches] SCREW MIN RATED MAX
M 2 1.9 2.2 2.5
M 6 26.1 38.9 52.2
M 8 101.8 150.5 199.1
M 10 194.7 292.1 389.4
M 12 336.3 495.6 663.8
FAN 230 V
50-60 HZ