Operating instructions

81
• check voltage at terminal X1.1 and X1.2 of the control device A70
• check semiconductor fuse and the fuses F2 and F3 on the controller card A1.
CAUTION
In any case, set the device de-energized and check if it is de-energized
Terminal X1.3 on the controller card A1 not connected.
if the semiconductor fuse is defective, then the following parameters must be checked in case of
transformer load for the operating modes TAKT and SSSD:
phase angle of the first half-wave (phase angle 1) = 60 degrees;
possibly optimize. Check for the model type 1P, 2P or 3P
Menu: Parameters/Operating mode/Number of phases controlled 1 2 3)
No load current
• RESET X5.2.12 is not jumpered for X5.1.14 (LED ON lit in red)
• supply voltage of the control device outside of the tolerable range
• controller lock X5.2.15 is not jumpered for X5.1.14 (LED PULSE LOCK is on)
no set point is set. Using the LBA-2, check the total set point (effective total), or measure set point
on X5.2.10 and X5.2.11.
- set points are not cleared
- parameterization of the set point inputs 20mA, 5V, 10V, does not matched to output of the
temperature controller
- check jumper X221 and X222 for current and voltage range
- parameters STA and STE of the control characteristic are wrong
- parameter for linkage of the set points is not set to ”ADD“
• parameters IEMA, UEMA, PMA are set too small
• controller parameters T
i
and K
p
are set too large.
CAUTION
Check fuses on the controller cards A1, A3, A5. In any case, set the device de-energized and check
if it is de-energized.
Load connection by the customer is missing (only for type 1P).
Check connection on A1 terminal X1.3.
• Check synchronization voltage at the control device A70 at the terminal blocks X7.1 and X7.2.
The thyristors are set to full scale
• Was the set point set via motor potentiometer function? Check value using the LBA-2.
• Check the control characteristic (Control start, Control end, Addition).
Controller feedback signal available? Check current transformer and voltage transformer
connections at the terminal blocks X7.1 and X7.2.
• Parameters Turn on-time T
s min
and Back pulse limit position, U
min
, I
min
, P
min
are larger than 0.
• Controller parameters Ti and Kp are set too small.
• Parameters I
max
, U
max
, P
max
are set too large or the load current is too small.
Measures in case of other maloperation of the device:
Evaluation of incident register (data logger) with LBA-2 or Thyro-Tool Family.
• Checking Thyro-P parameter.
• Checking wiring of Thyro-P.
• Correct number of controlled phases (parameters).
• With activated trouble signal relay Evaluation which faults led to a response, eliminate the fault.