It is possible to compare two sets of parameters (power controller or data file). It is thus possible, to
detect deviations from the desired configuration.
• line diagrams of process data with printing function, as well as storage of faults (diverse measured
values from different thyristor power controllers may be displayed simultaneously).
• bar diagram display
It is possible to simultaneously display several bar diagrams. Each diagram has its own window.
These can be adjusted in size and location. The configuration of the display may be stored.
• simultaneous display of data and parameters from several power controllers
• simultaneous connection of up to 998 Thyro-P power controllers using fiber optic distributors
• settings of the interface (baud rate, com...)
3.5 ERROR ACKNOWLEDGEMENT / DATA LOGGER
Unexpected operation of Thyro-P can be diagnosed by
• LEDs on the front panel of the control device
• comparing parameters with Thyro-Tool Family (where the changed parameters can be listed)
• reading out the error memory of the Thyro-P (data logger) with LBA-2 or Thyro-Tool Family
Errors and messages that occur will be recorded in the status register of the Thyro-P data logger at
the time they occur and will not be lost even after a power failure. Up to 16 entries are possible and
are displayed by LBA-2. If there are further entries, the initial ones will be overwritten, i.e., the 16
most up-to-date events will be accessible.
LBA-2: Data logs
dd.mm.yyyy hh:mm:ss
[Abbreviated error description]
The entries in the data logger are also available after power failure.