Operating instructions

29
3.1.4 EASYSTART
This menu enables the user to easily adjust the Thyro-P. For details on the EasyStart function and its
selection possibilities, see table LBA-2 MENU STRUCTURE.
When the user first starts LBA-2, the EasyStart will be displayed. Once the EasyStart prompt has
been conducted successfully on LBA-2, it will not appear each time LBA-2 is started. Irrespective of
this, EasyStart can be selected at any time if required via the LBA-2 menu.
3.1.5 LINE CHART / PROCESS DATA RECORDER
The line chart shows up to 6 values. The chronological process of these values is recorded auto-
matically and saved on the SD card (measuring interval is approx. 1sec.). Therefore a process data
recorder is provided to the user with up to 6 channels. The SD card has an amount of memory for
max. 6 channels which lasts approx. 2.7 years. Occurring messages (data logger) will also be saved
on the SD card and can be analyzed by LBA-2 Tool in combination with the saved signal sequence
of the 6 channels. For further details on how to set the line chart, please see table LBA-2 MENU
STRUCTURE.
The values selected for the line chart will be saved in the folder SD-Card:\Log. This is the case when
• the date changes (at 0.00 hours)
• the LBA-2 is switched off via OFF button
When the SD card is full, the oldest data will be deleted first and the current data then saved. The
data names correspond to the date the process data were measured:
The values selected for the line chart (up to six) will be saved on the 4GB SD card, which is included
with delivery under the file named SD-Card:\Log.
Example of LOG file:
131004.LOG (the process data were measured on October 4th, 2013
NOTE
In the event the LBA-2 is disconnected from the power supply without switching the OFF button
(e.g., when switching off the Thyro-P or when “removing „the LBA-2), the measured process data
will be lost and will not be saved.
3.1.6 LOAD / SAVE DATA
In addition to the process data from the line chart, Thyro-P parameter sets and LBA-2 settings can
be stored on the SD card.
The submenus can be found in table LBA-2 MENU STRUCTURE.
FIG. 8: EXAMPLE ENTRIES LOG FILE