Operating instructions
17
• Set point 2 (X5.2.11 - X5.1.13 ground) 0-5V default
The inputs set point 1, 2 are two electrically equal analogue inputs for current or voltage signals,
with subsequent A/D converter (resolution 0.025% of the final value), and they may be set to the
following signal ranges:
0(4)-20 mA (Ri = ca. 250 V / max. 24mA) see ATTENTION
0-5 V (Ri = ca. 8,8 kV / max. 12V)
0-10 V (Ri = ca. 5 kV / max. 12V)
The following table shall be used for the hardware configuration of the set point inputs (see also
FILE COMPONENT MOUNTING DIAGRAM CONTROL DEVICE, figure 10). If the hardware confi-
guration is changed, the Thyro-P parameters must be changed accordingly with the LBA-2 or the
Thyro-Tool Family.
X221 for Set point input 1
JUMPER X221 Signal range Set point input 1
closed* 0(4) -20mA (X5.2.10)
open 0-5V / 0-10V (X5.2.10)
X222 for Set point input 2
JUMPER X222 Signal range Set point input 2
closed 0(4)-20mA (X5.2.11)
open* 0-5V / 0-10V (X5.2.11)
* default
ATTENTION
If the open-circuit voltage of the connected set point exceeds 12V in the 20mA signal range, the
set point inputs can be destroyed, if the belonging JUMPER (X221, X222) is open.
Within the stated input ranges, these values with the control characteristic may be adjusted to any
common signal characteristic.
For a set point poti (e.g. 5-10 k
V
) 5V supply voltage can be taken from terminal X5.2.5 (Ri = 220
V
,
short-circuit-proof).
FIG. 1 CONTROL CHARACTERISTIC FOR U CONTROL