Operating instructions
13
For transport, assembly, installation, commissioning, operation and decommissioning, the safety
instructions contained in these operating instructions must be applied in any case and made
available to all persons handling this product.
CAUTION
It is important that preset parameters are not adjusted in any way that may cause the Power Con-
troller to overload. In case of uncertainties or missing information, please contact your supplier.
1.1 GENERAL
Thyro-P is a communication enabled SCR thyristor power controller. Below, it is also referred to
simply as power controller. The Thyro-P power controller can be installed everywhere where volta-
ges, currents or power have to be controlled precisely in 1- or 3-phase networks. Several modes of
operation and control, good coupling ability to process and automation technology, high control
precision by application of a 32 bit processor and simple handling ensure that Thyro-P is also suita-
ble for new applications.
Thyro-P offers new ways for mains load optimization:
• In operating mode TAKT, the optional digital mains load optimization of dASM ensures that mul-
tiple power controller applications can be used in an optimal way for the network so that system
perturbations are mainly avoided.
• For applications which have to use phase angle firing due to required high dynamic, Thyro-P...VSC
offers to minimize significantly harmonics by its VSC technology.
Thyro-P is suitable in particular for
• direct supply of ohmic loads
• for loads with large R
hot
/R
cold
ratio
• as primary power controller for a transformer with subsequent load
Due to use of high quality thyristors, the Thyristor Power Controller Thyro-P has a type range
up to 2900A, the nominal design loads reach up to about 2860kW.
1.2 SPECIFIC CHARACTERISTICS
Thyro-P is characterized by a multitude of specific characteristics, for instance:
• easy handling
• menu-driven user interface (options: LBA-2 with touch display, Thyro-Tool Family)
• type range 230-690 Volts, 5-2900A, single, double, triple phase
• broadband power supply AC 200-500V, 45-65Hz
• ohmic load and transformer load
• as well as load with large R
hot
/R
cold
for 1P and 3P
• soft start function for transformer load
• load circuit monitoring
• automatical rotating field recognition for 2P and 3P
• U, U
2
, I, I
2
, P control as well as without control
• operating modes TAKT, VAR, VSC_VAR, SSSD, MOSI (optional sub operating mode of TAKT and
VAR)
• mains load optimization dASM for applications with multiple power controllers in operating
mode TAKT
• control of analog set points or via interfaces
• fiber optic and RS232 interfaces as standard
• electrical separation according to EN 50178 chap. 3