Operating instructions
104
Due to European harmonization and international reconciliation, the standards will be subject to
years of adjustment and renumbering. The detailed schedule therefore contains the current stan-
dards as well, even if the date for their expiry has already been set. There is no product norm for
Thyristor Power Controllers, so that a sensible norm structure must be created from the correspon-
ding basic norms, which ensures safe application and opportunity for comparison.
CAUTION
Thyristor Power Controllers are non-valid devices for disconnection and may therefore be operated
only in connection with a suitable mains isolating device (for instance switch) connected on line side.
Approvals and conformities are available for Thyro-P:
• Quality standard according to ISO 9001
• Registration in acc. to UL 508, file no. E 135074
Investigated under consideration to Canadian National Standard C22.2 No. 14-95
• UL Markings:
· Field wiring terminal markings (see chapter 4 EXTERNAL CONNECTIONS)
· Use 60/75°C Copper Conductors only
· Tightening torque (pound inches) see chapter 11 TECHNICAL DATA
· Devices are suitable for the following short circuit current ratings:
Devices rated 300A
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical
Amperes, xxx Volts Maximum, When Protected by RK5 Class Fuses, sized max. 600A / 600V“
Devices rated 495A and 695A:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical
Amperes, xxx Volts Maximum“
NOTE:
xxx = max. allowable voltage depending upon rating of the device
• „Branch circuit protection must be provided and sized according National Electrical Code and any
additional local codes“
• CE conformity
Low Voltage Directive 73/23 EEC;
EMV Directive 89/336 EEC;
Marking Directive 93/68 EEC
• Interference suppression
The RegTP confirms the compliance with the interference suppression regulations for the power
control device
14. APPROVALS AND CONFORMITIES