User manual
3.3 Technical Data
Type rating
PDU 10 – 1 / PDU 10 – 2 2500 W max.
PDU 16 – 1 / PDU 16 – 2 4000 W max.
Mains connection parameters
Nominal connection voltage 220 / 230 / 240 Vac
Frequency 50 / 60 Hz
Nominal current
PDU 10 – 1 / PDU 10 – 2 10A
PDU 16 – 1 / PDU 16 – 2 16A
Mains connection by non-heating appliance plug
PDU 10 – 1 / PDU 10 – 2 IEC
320 C 14 (10A)
PDU 16 – 1 / PDU 16 – 2 IEC
320 C 20 (16A)
Connection cable
introduced from left side
PDU 10 – 1 / PDU 10 – 2 3 x 1.0 mm² 1 m
PDU 16 – 1 / PDU 16 – 2 3 x 1.5 mm² 1 m
Outputs
PDU 10 – 1 (6-way) 6 x non-heating appliance
sockets IEC 320 C 13
PDU 10 – 2 (6-way) 6 x shockproof sockets
DIN 49440
PDU 16 – 1 (7-way) 4 x non-heating appliance
sockets
IEC 320 C 13
3 x non-heating appliance
sockets IEC 320 C 19
PDU 16 – 2 (6-way) 3 x shockproof sockets
DIN 49440
3 x non-heating appliance
sockets IEC 320 C 19
EN
25