Datasheet
AEG PS - Protect B - EN - 09/2015 V2 - - TEMA - Technical data in this document does not contain any binding guarantees or warranties. Content only serves for information purposes and can be modified at any time. We will make binding
commitments only upon receipt of concrete enquiries and customer notification of the relevant conditions. Due to the non-binding nature of these terms, we assume liability neither for the accuracy nor completeness of the data provided here.
AEG is a registered trademark used under license from AB Electrolux.
AEG Power Solutions GmbH
Emil-Siepmann-Str. 32
59581 Warstein-Belecke
Germany
Tel.: +49 2902 763 0
Fax: +49 2902 763 169
www.aegps.com
Classification VI SS 333 acc. to IEC 62040-3 NAS B. 500 B. 750 B. 1000 B. 1500
Power type rating 500 VA 500 VA 750 VA 1000 VA 1500 VA
250 W 350 W 450W 700 W 900 W
Order number 600 001 7639 600 001 6600 600 001 6601 600 001 6602 600 001 6603
UPS INPUT
Nominal input voltage 220 VAC / 230 VAC / 240 VAC
Voltage range without battery mode 176 / 184 / 192 VAC – 264 / 276 / 288 VAC (depending on nominal input voltage)
Frequency (automatic detection) 50 Hz / 60 Hz ±5 %
Current consumption at full load (max.) 2.7 A 2.7 A 3.9 A 6.1 A 7.6 A
UPS OUTPUT
Nominal output voltage/AVR technology 220 VAC / 230 VAC (default) / 240 VAC -10 % +6 %
Nominal output voltage in battery mode 220 VAC / 230 VAC (default) / 240 VAC -10 % +5 %
Frequency in battery mode 50 Hz / 60 Hz ±0.1 Hz
Nominal output current (at 230 VAC) 2.1 A 2.1 A 3.2 A 4.3 A 6.5 A
Switchover time in the event of power failure <10 ms
Voltage wave form sinusoidal
Overload behavior (VI mode) 105% to <120% for 300 s / 120% to 150% for 10 s
Overload behavior (battery mode) 105% to 110% for 10 s
BATTERY
Type Sealed, maintenance-free (proprietary brand), hot-swappable
Integrated Yes
Nominal DC voltage (DC link) 12 VDC 24 VDC
Battery management Deep discharge protection, overload protection, automatic battery test
Autonomy time at 20% / 70% usage 60 min. / 12 min. 27 min. / 4.5 min. 27 min. / 4 min. 30 min. / 5.5 min 27 min. / 4.5 min.
Charging time (to 90% rated capacity) 7 h 5 h
COMMUNICATION
Interface USB as HID power device
User interface LCD display with digital indication of relevant UPS values: Input and output voltage [V] / usage [%] /
consumer load [(k)VA] and [(k)W] as well as autonomy time at current load [min.],
2 additional bar graphs for usage and current battery capacity / illuminated on/off button
Shutdown software (on CD) 5 network licenses for all common OS (e.g. Windows, Linux, Mac)
Alarms (acoustic/visual) Acoustic signal transmitter (can be deactivated) and detailed indication via LCD display (power failure,
overload, short-circuit, flat battery, replace battery, fan failure; AVR and charging unit failure
GENERAL DATA
Efficiency (normal mode) ≥94 %
Audible noise (1 m distance) ≤40 dB(A) ≤45 dB(A)
Fanless Speed-regulated fan
Operating temperature range 0 – 35 °C
Humidity 0 – 90 %
Operating altitude Up to 1000 m at nominal load
EMC conformity EN 62040-2 Class C1
Product safety EN 62040-1
Surge protection for data lines RJ11 (telephone, fax, modem) / RJ45 (Ethernet 10 Mbit/s / 100 Mbit/s)
Mains input IEC 320 C14
Consumer outputs 4 x IEC 320 C13 6 + 2 x IEC 320 C13
Housing color Black metal housing / with silver front panel
Dimensions approx. W x H x D (mm) 150 x 209 x 240 150 x 209 x 340
Approximate weight 6.8 kg 6.3 kg 6.8 kg 10.5 kg 11.5 kg
Scope of delivery Mains connection cable, device connection cable, USB communication cable,
“CompuWatch” management software (CD), 5 network licenses, operating instructions
Conformity CE, EN 50581
Separate bar graphs to
indicate UPS usage and
battery capacity
Status window to display
operating status and
detailed fault indication
Retrieval of measured
values for UPS input and
output and consumer load
UPS input and output voltage [VAC]
UPS usage [%]
Expected autonomy time in battery mode [MIN]
Consumer load [(k)VA] and [(k)W]
Protect B Display