User manual

10
5. SPECIFICATION
MODEL Protect alpha. 1200
CAPACITY VA / W 1200 VA / 600 W
INPUT Voltage 120 V AC or 230 V AC
Voltage range 85 – 145 V AC or
170 – 280 V AC
OUTPUT Voltage
Voltage regulation
(battery mode)
± 10 %
Frequency 50 Hz or 60 Hz
Frequency regulation
± 1 Hz (battery mode)
Output waveform Modified sine wave
BATTERY Battery type 12 V 7 Ah x 2
Recharge time 6 hours to 90 % after complete
discharge
TRANSFER TIME Typical 4 – 8 ms
INDICATOR Normal Green LED
AC mode Green LED
Battery mode Yellow flashing LED
Fault mode Red LED
AUDIBLE ALARM Backup mode Sounding every 10 seconds
Low battery Sounding every 1 second
Overload Sounding every 0.5 seconds
Fault Continuously sounding
PROTECTION Full protection Discharge, overcharge,
and overload protection
PHYSICAL Dimension (mm) 365 (L) x 139 (W) x 195 (H)
WEIGHT Net weight 8.6 kg
ENVIRONMENT Operating environment 0 °C – 40 °C
Noise level Less than 40 dB
120 V AC or 230 V AC