Datasheet
2
Classification VFI SS 211 acc. to IEC 62040-3 D. 1000 D. 1500 D. 2000 D. 3000
Power type rating 1000 VA 1500 VA 2000 VA 3000 VA
900 W 1350 W 1800 W 2700 W
Part number
(UPS including integrated battery system)
600 000 8434 600 000 8436 600 000 8437 600 000 8438
Part number (additional battery pack) 600 000 8441 600 000 8442 600 000 8443
UPS INPUT
Input voltage 220 V AC / 230 V AC / 240 V AC
Voltage range without battery mode
(load dependent)
120 – 276 V AC 140 – 276 V AC
Frequency (auto selection) 50 Hz / 60 Hz ± 5 Hz
Mains current (system reaction)
λ ≥0.99 (THDi ≤8 %)
Current consumption at nominal load (max.) 4.8 A 7.2 A 9.6 A 13.7 A
UPS OUTPUT
Rated output voltage (adjustable) 200 V AC / 208 V AC / 220 V AC / 230 V AC (default) / 240 V AC ±2%
Frequency in battery- /
frequency converter mode
50 Hz / 60 Hz ±0.25 Hz
Output current (at 230 V AC) 4.3 A 6.5 A 8.7 A 13 A
Transfer time at mains outage 0 ms (without interruption)
Voltage waveform Sinusoidal, distortion THD <3 %
Overload response (double conversion mode) <130 % for 5 min. / 130 % – 150 % for 15 s
Overload response (battery mode) <130 % for 12 s / 130 % – 150 % for 2 s
Crest factor 3 : 1
Short circuit response Short circuit proof (4 x I
N
for 100 ms)
BATTERY
Type Sealed, maintenance free (proprietary brand), integrated, hot swappable
Rated voltage (linked) 36 V DC 48 V DC 72 V DC
Battery management Temperature compensated with discharge protection,
automatic battery test (programmable) and battery pack detection
Charging time (to 90 % rated capacity) 3 h
COMMUNICATION
Interfaces (dual monitoring) RS232, USB, communication slot (can be used parallel with RS232 / USB),
input contact for emergency shutdown, programmable potential free contact
Shutdown software (on CD) 5 network licenses for all common OS (e.g. Windows, Linux, Mac, Unix, Sun etc.)
Failure indicators (acoustic /visual) 3 LED’s with traffic light display, detailed indication via LCD display
(alarms: at mains failure, overload, battery charging, battery replacement, fan fault,
data logger – with clear text display incl. date and time history)
GENERAL DATA
Efficiency (ECO+ mode) >95 % >98 %
Efficiency at nominal load
(double conversion mode)
≥88 % >88 % >89 % ≥90 %
Audible noise (1 m distance) <44 dB(A) < 45 dB(A) <52 dB(A)
Operating temperature range 0°– 40 °C
Humidity 0 – 95 % (without condensation)
Operation altitude Up to 3000 m at nominal load
EMC conformity EN 62040-2 Class C1, EN 61000-3-2, EN 61000-3-3
Product safety EN 62040-1
Number of outputs (switchable)
automatically locked
6 x IEC 320 C13 (2+2) 8 x IEC 320 C13 (2+2) 6 x IEC 320 C13 (3+3)
+ 1 x IEC 320 C19
Housing Blackline metal case with aluminum front
Dimensions approx. W x H x D (mm) UPS 482.6 (19") x 88 (2 U) x 430 482.6 (19") x 88 (2 U) x 600
Dimensions approx. W x H x D (mm) battery 482.6 (19") x 88 (2 U) x 430 482.6 (19") x 88 (2 U) x 430
Weight approx. UPS incl. integrated battery 16 kg 19.5 kg 19 kg 29.5 kg
Weight approx. battery extension unit 23 kg 28 kg 41 kg 41 kg
Shipment Mains input cord (1 x EU, 1 x UK), UPS management software “CompuWatch” (CD),
communications cables (RS232 & USB), operating instructions, rack rails,
device cables: 3 x IEC 320 C13 (D. 1000 – D. 2000), 3 x IEC 320 C13 +1 x IEC 320 C19 (D. 3000)
Conformity CE