Datasheet

AEG PS - Protect A - EN - 10/2014 V2 - Technical data in this document does not contain any binding guarantees or warranties. Content only serves for information purposes and can be modified at any time. We will make binding
commitments only upon receipt of concrete enquiries and customer notification of the relevant conditions. Due to the non-binding nature of these terms, we assume liability neither for the accuracy nor completeness of the data provided here.
AEG is a registered trademark used under license from AB Electrolux.
AEG Power Solutions
Approach your local AEG Power Solutions
representative for further support.
Contact details can be found on:
www.aegps.com
Protect A
SPecificAtion
Classification VI SY 322 acc. to IEC 62040-3 A. 500 A. 700 A. 1000 A. 1400
Power type rating 500 VA 700 VA 1000 VA 1400 VA
300 W 420 W 600 W 840 W
Part number 600 000 6435 600 000 6436 600 000 6437 600 000 6438
UPS INPUT
Input voltage 220 V AC / 230 V AC / 240 V AC
Voltage range without battery mode 170 – 280 V AC
Frequency (automatic selection) 50 Hz / 60 Hz ±5 Hz
UPS OUTPUT
Rated output voltage / AVR technology 230 V AC
Rated output in battery mode ±10 %
Frequency in battery mode 50 Hz / 60 Hz ±1 Hz
Nominal output current (at 230 V AC) 2.2 A 3 A 4.3 A 6.1 A
Transfer time at mains outage 2 – 6 ms (typical)
Voltage waveform Approximated sinusoidal
Overload protection Yes
BATTERY
Type Sealed, maintenance free (proprietary brand)
Autonomy time for 1 PC with 17" TFT ~15 m in . ~20 min. ~30 min. ~40 min.
Exhaustive discharge protection /
protection against excess load
Yes
Charging time (to 90 % of rated capacity) 8 h
COMMUNICATION
Interfaces USB and RS232 (with status messages measured values)
Shutdown software (on CD) Included in delivery for all major operating systems (e.g. Windows, Linux, Mac)
Alarm messages (acoustic /visual) Mains failure, overload, battery discharged, replace battery, fault
LCD display for input and
output voltage [V] /
efficiency [%] / autonomy time [min.]
GENERAL DATA
Audible noise (1 m distance) <40 dB(A) <45 dB(A) (AC-operation <40 dB(A))
Fanless Speed controlled fan
Operating temperature range 0° – 40 °C
Humidity 0 – 90 % (without condensation)
Operation altitude Up to 1000 m at nominal load
EMC conformity EN 62040-2 Class C2, EN 61000-3-2, EN 61000-3-3
Product safety EN 62040-1
Data line protection
RJ11 (telephone, fax, modem)
RJ11 / RJ45 (add. network),
Ethernet 10 and 100 Mbit/s
Outputs 3 + 1 x IEC 320 C13 4 + 2 x IEC 320 C13
Equipment color Blackline
Dimensions approx. W x H x D (mm) 100 x 140 x 330 145 x 205 x 405
Weight approx. 6 kg 6.5 kg 9.5 kg 10 kg
Shipment Mains input cord (1 x EU, 1 x UK), 2 device connecting cables,
management software “CompuWatch” (CD) incl. 1 network license
USB and RS232 communication cable, operating instructions
Conformity CE