Technical data
General recommendations
Inverter Selection
Inverter selection
(V)
100 500 1,000 2,000 5,000 10,000
Steca AJ Steca Solarix PI
Inverters
48
24
12
1,000 2,000 3,000 5,000 (W AC)
Steca
Compact
Steca
HPC
Steca
XPC
100,00010,000 20,000 50,000
Inverters with battery chargers
48
24
12
(V)
Steca
Xtender XTM
Steca
Xtender XTH
(W AC)
22|
Steca Elektronik GmbH | 87700 Memmingen | Germany | Fon +49 (0) 8331 8558-0 | Fax +49 (0) 8331 8558-132 | www.steca.com
|23
a high overload capacity, particularly in the start-up
phase. The battery must also possess a large enough
capacity so that sufficient currents are made availa-
ble to the inverter in the start-up phase. We recom-
mend choosing the battery size according to the fol-
lowing formula: the battery capacity should be at
least five times as large as the rated power of the
inverter divided by the rated voltage of the battery.
C
batt
≥ 5 h * P
nom
/ U
nom
P
nom
is the rated power of the inverter in watts and
U
nom
is the rated voltage of the battery.
Selecting the system voltage
The power requirement of the loads should be the
decisive factor when choosing the system voltage.
The higher the power, the higher the system voltage.
If no 12 V DC loads are connected to the system,
a higher system voltage of 24 V or 48 V should be
chosen in order to reduce the alternating currents,
and thus the losses on the DC side. Inverters also
generally work more effectively with a higher input
voltage. All in all, a higher system voltage leads to
the system having a greater efficiency, since losses
are reduced
Cable lengths and cross sections
Direct currents in inverter systems are typically lar-
ge. For this reason, it is important to dimension
the cables between the battery and the inverter ap-
propriately. Always connect the inverter directly to
the battery. The cable you use should be as short
as possible. In addition, the cable cross section
should match the expected flow of current. In case
of doubt, a thicker cable should be chosen. This can
have a significant influence on the overall behaviour
of the system. Using thick and short cables can limit
losses and thus allow you to create a system with a
better level of efficiency and/or better performance.
If the cables on the direct current side of the inver-
ter are included in the delivery, these should not be
lengthened, and a smaller cross section should not
be used.
General recommendations
for alternating current and hybrid systems.
Sine wave inverters
In contrast to so-called square wave or trapezoidal
inverters (grey square curve), Steca sine wave inver-
ters produce a real and precisely controlled sinus
wave (red sinus wave) at their output. The sinus
wave inverters assure that all loads which are sui-
table for grid operation can also be operated on a
solar home system without any problems. Further-
more, they offer the advantage that no significant
noises are produced in the inverter and there is no
loud background noise to be heard on a connected
radio, for example.
Selecting an inverter
The power of the inverter must be selected according
to the way it will be used. The sum of the power of
all loads must not exceed the rated power of the in-
verter. The maximum power of the inverter must be
able to cover the starting currents of the loads.
In order to allow the connection of more loads, Steca
recommends overdimensioning the inverter.
Selecting the PV generator and solar charge
controller
The solar module array has to be adjusted to the local
sunlight conditions and the system‘s energy require-
ment. In order to avoid stagnation times, the PV gene-
rator must also provide enough power during months
with little solar radiation in order to cover the require-
ment of the connected loads.
The chosen solar charge controller must also be sui-
table for the maximum short-circuit current of the PV
generator and the maximum load current. In some ap-
plications, however, technical properties also play an
important role in the choice of solar charge controller.
This may mean that a high-performance solar charge
controller with corresponding additional functions is
used in a system with a low output.
In order to keep the initial investment small, we recom-
mend planning the size of the PV generator and bat-
tery according to the current energy consumption and
choosing a solar charge controller which will allow the
system to be expanded later.
Selecting the battery
In order to also be able to supply loads with high
requirements without any problems, the size of the
battery must be chosen with care. Some critical loa-
ds such as fridges, freezers, pumps and motors need
extremely high starting currents in their start-up
phases. In order to be able to power such loads, it
is important to use a high-performance inverter with
P
nom
inverter U
nom
battery Battery capacity
200 W 12 V > 100 Ah
500 W 12 V > 200 Ah
1,000 W 12 V > 400 Ah
2,000 W 12 V > 800 Ah
2,000 W 24 V > 400 Ah
3,500 W 24 V > 700 Ah
3,500 W 48 V > 350 Ah
5,000 W 48 V > 500 Ah
7,000 W 48 V > 700 Ah
Sine wave
Square wave










