Specifications

Specifications A
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
73 of 155
Total standby-current of these loads must draw less than 236 mA to maintain continuous standby operation for
twenty-four hours followed by five minutes of alarm.
Current loading calculations do not include the combined IDC currents of the Quaestor-SZU Releasing Fire Control
Panel. These combined IDC currents are negligible in comparison to fire control panel, ancillary device and NAC
currents of the Quaestor-SZU Releasing Fire Control Panel and are therefore excluded from the current loading
calculation.
Ground Trouble Indication
A ground trouble indication occurs when a minimum of 30K Ohms exists between earth-ground and the following
VDC terminals of the fire control panel:
AUX 24V
POWER, STATUS UNITS
NAC 1, NAC 2 and NAC 3
ZONE 1, ZONE 2, ZONE 3
MODE SELECT
MAN RELEASE
•ABORT
REL. PRES. SWITCH
•EXTING.
•LOW P. SWITCH
Field Wiring
The following specifications identify the range of acceptable wire gages for field wiring, battery and power
connections:
Terminal Wire Range
AUX 24V 14 - 18 AWG
REMOTE CONTROL No Connection (NC)
DATA - STATUS UNITS
14 - 18 AWG
POWER - STATUS UNITS 14 - 18 AWG
NAC 1, NAC 2 14 - 18 AWG
ZONE 1, ZONE 2, ZONE 3 14 - 18 AWG
2ND SOUNDER 14 - 18 AWG