Specifications
Contro
l
Panel:
Specifications A
Standby and Alarm Power-Limitations
The following stan
dby and alarm power limitations are provided below for the Quaestor-SZU Releasing Fire
Power Source Standby Operation Alarm Operation
Power Supply Primary, 115 VAC
125 VA
Power Supply Primary, 230 VAC
126 VA
Current Draw From Battery
In Mains Fail Condition
100 mA, 86 mA with internal
sounder silenced
250 to 620 mA
Maximum Current Draw
The m
aximum current draw of the Quaestor-SZU Releasing Fire Control Panel cannot exceed 2.0 A. Outputs of the fire
control panel can be loaded with any combination of currents as long as the total current does not exceed 2.0 A.
All calculations of maximum current draw must include the 620 mA current required to operate
the Quaestor-SZU Releasing Fire Control Panel while in an alarm condition.
Outputs of the Quaestor-SZU Releasing Fire Control Panel are listed below:
Terminals Current Rating
Quaestor-SZU Releasing
Fire Control Panel
620 mA
Exting. 1.0 A
Status Unit, Power 500 mA
AUX 24V 500 mA
NAC 1
Reference “Notification Appliance Circuit (NAC)” of this appendix for current
ratings.
NAC 2
Reference “Notification Appliance Circuit (NAC)” of this appendix for current
ratings.
NAC 3
Reference “Notification Appliance Circuit (NAC)” of this appendix for current
ratings.
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation
Manual
Revision E03.04
SHM80001
71 of 155