The figure below illustrates the J2 Jumper location on the Ancillary Board:
Figure 6-4
J2 Jumper Location
Relay Contacts
Relay contacts of the Ancillary Board provide volt free changeover relay contacts for local control and signalling. The
relay contacts are rated for switching signalling circuits only and the maximum ratings should not be exceeded under
any circumstances.
Relay contact of the Ancillary Board include:
Zonal Fire Relays Zonal fire relays on the Ancillary Board are labelled Zone 1 FIRE, Zone 2 FIRE and Zone 3
FIRE. The zonal fire relays operate in conjunction with the activation of zones 1 to 3 on the fire
control panel. Zonal fire relays remain activated until the fire control panel is reset.
MAN MODE Relay The MAN MODE relay operates when the extinguishant system is switched to manual only
mode and switches off when the system is switched to Automatic and manual mode.
DISAB Relay The DISAB relay operates when the extinguishant system is disabled via access level 2
option [dE].
REL Relays The REL relay operates when the released condition has been established at the fire control
panel.
ACT Relay The ACT relay operates when the activated condition (extinguishant release countdown) has
been established at the fire control panel.
HOLD Relay The HOLD relay operates when the system is in the Hold condition.
EXTR Relay The EXTR relay operates when the fire control panel is operating the extract fan output.
MAN REL Relay The MAN REL relay operates when a manual release input occurs on the fire control panel.