Abort Function
Abort is a is a temporary function that suspends the releasing count-down after contacts on a momentary-switch are
closed. Suspension of the releasing count-down occurs at 10 seconds. Activating the abort function prior to 10 seconds
continues the releasing count-down until the timer reaches 10 seconds.
Activating the abort function after 10 seconds causes an immediate suspension of the releasing count-down and the
timer holds at 10 seconds. The releasing count-down re-starts at 10 seconds when contacts on the momentary-switch
are opened. A releasing event occurs when the count-down timer reaches zero. An abort function overrides a manual
release function when the manual release is activated before the abort. The manual release function overrides the abort
function when the abort is activated before the manual release.
Silence/Sound Alarms
The Silence/Sound alarm button can only be operated at access level two which means that the Enable Control key
must be inserted and turned to the right. To silence the NACs, insert the Enable Control key, turn to the right and press
the Silence/Sound alarm button.
When the NACs have been silenced, the Zone Fire LEDs will change from flashing to a steady state. Pressing the
Silence/Sound alarm whilst the fire control panel is in this silenced condition, will cause the NACs to operate again.
The NACs can be toggled on and off with the Silence/Sound alarm button as required.
Reset
The reset command restores operation of the Quaestor-SZU Releasing Fire Control Panel from alarm and trouble
conditions. Latched inputs of the extinguishant circuit are reset after the countdown timer expires.
The reset command can be configured to operate before the countdown timer has expired. The configuration programs
the command to reset the extinguishant output during the imminent release phase.
Reference Configuration Code, C29 of this section to program the reset command to operate during the imminent
release phase of the extinguishant output.
The reset command can be operated with or without activation of the Trouble Relay.
To reset the fire control panel without activation the Trouble Relay:
To reset the fire control panel with activation of the Trouble Relay:
1 Turn the key of the Enable Access to the right to obtain Access Level 2 of the menu.
2 Press the Reset button for less than ten seconds.
The fire control panel will restore from the alarm or trouble condition and the Trouble Relay will not activate.
1 Turn the key of the Enable Access to the right to obtain Access Level 2 of the menu.
2 Press the Reset button for ten seconds or more.
The fire control panel will restore from the alarm or trouble condition and the Trouble Relay will activate
ten seconds after operation of the reset command.