Specifications

Programming and Operating 4
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
45 of 155
Operating the Fire Control Panel
Access levels are provided for controls and programming on the Quaestor-SZU Releasing Fire Control Panel. Access
Level 1 provides restricted controls, Access level 2 provides less restricted controls with limited programming and
Access Level 3 provides unrestricted controls and programming.
Access Level 2
To operate the Quaestor-SZU Releasing Fire Control Panel in Access Level 2:
Functions and Codes
Functions and codes for operating the Quaestor-SZU Releasing Fire Control Panel in Access Level 2 are
described below:
1 Turn enable key-switch to get to access level 2.
2 Press Mode button until the required function is displayed in the System Mode LED.
3 Press the Select button to scroll to the required zone number then press Enter.
The “select dot” at the bottom of the System Mode LED flashes to confirm that the selected-function is active.
Function Terminal Codes Description
Test Zones ZONE 1 t1 Select codes t1, t2 or t3 to place Zones 1, 2 or 3 in Test Mode.
Zones in Test Mode automatically reset 3 seconds after
operating. The Test Mode On and Zone Trouble/On Test/
Disabled indicators illuminate when zones 1, 2, or 3 are in
Test Mode.
ZONE 2 t2
ZONE 3 t3
Disable Zones ZONE 1 d1 Select codes d1, d2 or d3 to disable Zones 1, 2 or 3. Disabling
Zones does not provide fire or trouble indications on the fire
control panel. The General Disablement and Zone Trouble/On
Test/Disabled indicators illuminate when zones 1, 2, or 3 are
disabled.
ZONE 2 d2
ZONE 3 d3
Disable NAC 1 NAC1 db Select the code db to disable the NAC1 output. The General
Disablement and NAC Trouble/ Disabled indicators illuminate
when NAC1 is disabled.
Disable
1st Stage Relay
1ST STAGE dP Select the code dP to disable the 1ST STAGE relay. The
General Disablement indicator illuminates when the
1ST STAGE relay is disabled.
Disable
2nd Stage
Relay
2ND STAGE dA Select the code dA to disable the 2ND STAGE relay. The
General Disablement indicator illuminates when the
2ND STAGE relay is disabled.