Specifications
Programming and Operating 4
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
43 of 155
Code Function Description
C61 Zone 1 operates through I.S.
Barrier
Select only when detectors are connected to compatible I.S. barriers.
Any combination can be selected.
C62 Zone 2 operates through I.S.
Barrier
C63 Zone 3 operates through I.S.
Barrier
C71 Zone 1 short circuit indicates
alarm
Changes the trigger threshold of the zone so that the fire control panel
can be used on older systems that do not have short circuit
monitoring. Any combination can be selected.
C72 Zone 2 short circuit indicates
alarm
C73 Zone 3 short circuit indicates
alarm
C81 Zone 1 non-latching Renders the zone self-resetting so that it can be used to receive
signals from other systems and resets when the input is removed. Any
combination can be selected.
C82 Zone 2 non-latching
C83 Zone 3 non-latching
CA1 Zone 1 device alarm must be
present for 30 seconds
Input delay. Any combination can be selected.
CA2 Zone 2 device alarm must be
present for 30 seconds
CA3 Zone 3 device alarm must be
present for 30 seconds