Indicator Description
Sys Fuse Trbl The power rating of the power supply has been exceeded and the system fuse has
operated. Remove and review all loads and re-connect one at a time until over rated
circuit trips fuse to identify faulty circuit.
S1, S2 and S3 Trbl A short or open circuit exists on NAC outputs. Remove wiring and reconnect EOL
resistors. Check NAC circuit wiring.The S3 LED will be accompanied by the front panel
Flooding zone trouble LED to indicate a common trouble condition within the releasing
agent section of the fire control panel.
Exting Trbl A short or open circuit exists on the releasing agent output. Remove wiring and
reconnect EOL resistors. Check releasing agent circuit wiring. The Exting trouble LED
will be accompanied by the front panel Flooding zone trouble LED to indicate a common
trouble condition within the releasing agent section of the fire control panel.
Abort Trbl A short or open circuit exists on the abort switch input. Remove wiring and reconnect the
EOL. Check abort circuit wiring. The Abort Trbl LED will be accompanied by the front
panel Flooding zone trouble LED to indicate a common trouble condition within the
releasing agent section of the fire control panel.
Manual Release Trbl A short or open circuit on the manual release switch input. Remove wiring and reconnect
EOL. Check manual release circuit wiring. The Manual release trouble LED will be
accompanied by the front panel Flooding zone trouble LED to indicate a common trouble
condition within the releasing agent section of the fire control panel.
Mode Trbl A short or open circuit exists on the mode switch input. Remove wiring and reconnect the
EOL. Check mode circuit wiring. The Mode Trbl LED will be accompanied by the front
panel Flooding zone trouble LED to indicate a common trouble condition within the
releasing agent section of the fire control panel.
Release Trbl A short or open circuit exists on the released pressure switch input. Remove wiring and
reconnect end of line. Check released pressure switch circuit wiring. The Released Trbl
LED will be accompanied by the front panel Flooding zone trouble LED to indicate a
common trouble condition within the releasing agent section of the fire control panel.
Low Pres Trbl A short or open circuit exists on the low pressure switch input. Remove wiring and
re-connect the EOL. Check low pressure switch circuit wiring. The Low pres trouble LED
will be accompanied by the front panel Flooding zone trouble LED to indicate a common
trouble condition within the releasing agent section of the control panel.
Tell Tale The panel mounted or remote manual release button has been pressed.
Can only be reset by pressing processor reset and W/DOG reset or powering down the
fire control panel.