Installation 3
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
25 of 155
Reference Section 5, Maintenance for replacing the standby-batteries.
The figure below illustrates standby-battery connections in the Quaestor-SZU Releasing Fire Control Panel:
Figure 1-5
Standby-Battery Connections
The illustrated series connection above provides a standby voltage of 24 VDC required by the Quaestor-
SZU Releasing Fire Control Panel.
L
FUSE
N
7 AH Battery
Negative Battery Lead
( Black Cable )
Jumper-Lead
7 AH Battery
Positive Battery Lead
( Red Cable )
Each standby-Battery is 12 VDC, 7 Amp Hour and sealed-rechargeable
-
+
Low
Pres. Tale
Tell Terminate
Release
W/Dog
Reset
Processor
Reset
Exting.
Mon.
Write
Enable
Exting. ReleaseModeMan.Rel.Abort
Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.
NAC3NAC1 NAC2Sys.FuseEarth
Trbl.Trbl.Trbl.Trbl.Trbl.
Comms
Low
Batt.
Trbl.
Aux.24V
Trbl.
CPU
Mains
Fail
(+1)(+10)
Enter System ModeSelectModeReset Lamp Test
(+100)
Silence/Sound
Alarm
On Test/Disabled
Test Mode On
General
Disablement
System Trouble
Buzzer Silenced
2nd Stage Output
Extract Fan On
Abort Activated
Releasing Trouble
Silence
Buzzer
Enable Access
EXTRACT
SWITCH
REL PRES.
SWITCH
LOW P.EXTING.ABORT
RELEASE
MAN.
SELECT
MODE2ND STAGE1ST STAGENA C3POWERDATA
STATUS UNITS
REMOTE
CONTROL
AUX
24V
CNONOCNCNOCNC
ZONE 3
E
ZONE 1 ZONE 2NAC2NAC1
RSTR0V SIL AL FLT NOCNCNOCNCNOCNC
FIRE RELAYLOCAL FIRETROUBLE RELAY
24V DC
Power On
General System Status Fire In Zone
123
Zone Trouble/
Disablements/
Supervisory
Releasing Status
Fire
Delay On
NAC Trouble/
Disabled
Power Trouble
General Trouble
Manual Release
Extinguishant
1st St age Output
Release
Imminent
Auto &
Manual
Manual
Only
Extinguishant
Released
Low
Pressue
1st Sta ge
Activated
Pull Down - Push Button
Manual
Extinguishant Release