Specifications
UL 864 Permitted Configurations G
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
147 of 155
Program Feature or Option Permitted in UL 864 ? (Y / N) Possible Settings Settings Permitted
In UL 864
Zone 1 Operates Through
I.S. Barrier
Code: C61
N Enable / Disable Disable
Zone 2 Operates Through
I.S. Barrier
Code: C62
N Enable / Disable Disable
Zone 3 Operates Through
I.S. Barrier
Code: C63
N Enable / Disable Disable
Zone 1 Short Circuit
Indicates Alarm
Code: C71
Y Enable / Disable Enable / Disable
Zone 2 Short Circuit
Indicates Alarm
Code: C72
Y Enable / Disable Enable / Disable
Zone 3 Short Circuit
Indicates Alarm
Code: C73
Y Enable / Disable Enable / Disable
Zone 1 Non-Latching
Code: C81
N Enable / Disable Disable
Zone 2 Non-Latching
Code: C82
N Enable / Disable Disable
Zone 3 Non-Latching
Code: C83
N Enable / Disable Disable