NAC 1 and NAC 2 of the Quaestor-SZU Releas-
ing Fire Control Panel can each operate a maxi-
mum of seven Amseco SL-1224 strobes when
configured for 15cd outputs and synchronized
with an Amseco SMD10-3A synchronization
module.
Gentex
NAC 1 and NAC 2 of the Quaestor-SZU Releas-
ing Fire Control Panel can each operate a maxi-
mum of six Gentex GES3-24 strobes when con-
figured for 15cd outputs and synchronized with
a Gentex AVSM synchronization module.
System
Sensor
NAC 1 and NAC 2 of the Quaestor-SZU Releas-
ing Fire Control Panel can each operate a maxi-
mum of eight System Sensor S1224MC strobes
when configured for 15cd outputs and synchro-
nized with a System Sensor MDL synchroniza-
tion module.
Cooper/
Wheelock
NAC 1 and NAC 2 of the Quaestor-SZU Releas-
ing Fire Control Panel can each operate a maxi-
mum of eight Cooper/Wheelock RSS-24MCW
strobes when configured for 15cd outputs and
synchronized with a Cooper/Wheelock SM-24
synchronization module.
Notification Appliance Circuit
The following statements for NAC synchronization are
necessary for UL qualification and exclude device-loading
combinations that are common in most FACP installations: