Specifications
Wiring Diagram D
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
124 of 155
9
Initiating Device Circuit
Adjustable
Extinguishant Output
Delay
Adjustable 0 to 60 seconds
(+/- 10%) in 5 second intervals
Extinguishant Duration
Adjustable 60 to 300 seconds (+/
- 10%) in 5 second intervals
Mode Select
No Connect (NC) terminal
Short Circuit Threshold
Adjustable
Remote Control Inputs
No Connect (NC) terminals.
File: S8485, Part Number: Man-SHM80004
Revision E07.03, Date: 26 March 2013
Ratings
Maximum Operating
Voltage
21.6 VDC
Maximum Short Circuit
Current
65 mA
Maximum Line
Impedance
20.3 Ohms