Specifications

Wiring Diagram D
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
121 of 155
6
File: S8485, Part Number: Man-SHM80004
Revision E07.03, Date: 26 March 2013
Ground Fault Indications
A ground fault indication occurs when 30K Ohms or less exists
between earth-ground and the following field terminals of the
Quaestor-SZU Releasing Fire Control Panel:
 AUX 24V
 POWER, STATUS UNITS
 NAC 1, NAC 2 and NAC 3
 ZONE 1, ZONE 2, ZONE 3
 MODE SELECT
 MAN RELEASE
 ABORT
 REL. PRES. SWITCH
 EXTING.
 LOW P. SWITCH
 DATA, STATUS UNITS