Specifications

Wiring Diagram D
SHM80001
SAFETY HI-TECH
Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual
Revision E03.04
120 of 155
5
File: S8485, Part Number: Man-SHM80004
Revision E07.03, Date: 26 March 2013
Standby-Battery Type
Two 12 VDC, 7 AH, sealed
lead acid, batteries
Standby-Battery Charging
Two standby batteries wired
in series
Charge Current
700 mA maximum
Output Current
0 - 2 Amps
Standby-Operating Time
24 Hours
Battery Charge Voltage
27.6 VDC
Fire Control Panel Current
Draw From Battery
While In Mains Fail,
Standby And Not in Alarm
100 mA with buzzer sounding
Maximum Current Draw
of FACP, In Alarm
620 mA (Current does not
include loads from NACs,
Solenoid, Status Units,
Ancillary Boards and
Auxiliary equipment)
Maximum Current Draw
From Batteries
2 Amps
Rechargeable Battery Circuit