Model AFC-500 AFC-11001 AFC-11003 AFC-11005 AFC-11010 AFC-11015 AFC-31020 AFC-31030 AFC-31045 AFC-31060
Capacity (kVA) 0.5 1 3 5 10 15 20 30 45 60
Voltage 110V or 220V ±15%, 1 Phase 220V ±15%, 1 Phase 380V ±15%, 3 Phase 3 or 4 wire
Frequency 50Hz ± 3Hz, 60Hz ± 3Hz
Output
(AC)
Phase Single Phase
Voltage Low 0~150V 5V ~ 150V (L-N)
High 0~300V 10V ~ 300V (L-N)
Frequency 47 ~ 63Hz, 50Hz, 60Hz, 400Hz, 2F (2 x Input Frequency), 4F (4 x Input Frequency)
Option: 40 ~ 500Hz
Maximum Current
Low 4.2A 8.4A 25A 42A 84A 126A 168A 250A 375A 500A
High 2.1A 4.2A 12.5A 21A 42A 63A 84A 125A 188A 250A
Frequency Stability ≤0.01%
Load Regulation ±0.2% ±1% (linear load)
Total Harmonic Distortion ±0.2% ±2% (linear load)
Transient Response 50us Max. 2ms Max.
Meter /
Res.
4 Dig. Freq. Met. Res. 0.1Hz
4 Dig. Voltmeter Res. 0.1V
Digit Ammeter 0.001A 0.01A 4 Digit Ammeter / Res. 0.1A 5 Digit Ammeter / Res.0.1A
4 Dig. Wattmeter 0.1W 1W Option
Protection Input Circuit Breaker, Output Circuit Breaker, Electronic Circuits Instant Trp for Over Voltage, Over Load, Over Temperature,
Short Circuit Protection and Alarm System
Envionment
Ambient Temp. 0°C ~ 45°C
Relative Hum. 0 ~ 90% Non-condensing
Altitude 1500 meter
Dimensions W x H x D (mm) 430x520x200 430x520x720 430x750x990 600x970x1240 800x600x1600
Net Weight (kg) 44 89 73 89 150 171 280 333 418 571
Model AFC-33006 AFC-33010 AFC-33020 AFC-33030 AFC-33045 AFC-33060 AFC-33075 AFC-33100 AFC-33150 AFC-33180
Capacity (kVA) 6 10 20 30 45 60 75 100 150 180
Voltage 380V ±15%, 3 Phase 3 or 4 wire
Frequency 50Hz ± 3Hz, 60Hz ± 3Hz
Output
(AC)
Phase Three Phase
Voltage Low 5V ~ 150V (L-N)
High 10V ~ 300V (L-N)
Frequency 47 ~ 63Hz, 50Hz, 60Hz, 400Hz, 2F (2 x Input Frequency), 4F (4 x Input Frequency)
Option: 40 ~ 500Hz
Maximum Current
Low 16.7A 27.8A 55.6A 83.3A 125A 167A 208A 278A 417A 500A
High 8.3A 13.9A 27.8A 41.7A 62.5A 83.3A 104A 139A 208A 250A
Frequency Stability ≤0.01%
Load Regulation ≤ ±1% (linear load)
Total Harmonic Distortion ≤ ±2% (linear load)
Transient Response 2ms Max.
Meter /
Res.
4 Dig. Freq. Met. Res. 0.1Hz
4 Dig. Voltmeter Res. 0.1V
Digit Ammeter 4 Digit Ammeter / Res. 0.1A 5 Digit Ammeter / Res.0.1A
4 Dig. Wattmeter Option
Load Balance or No Load: ≤ 1°, 100% Unbalance: ≤ 2° (measured at 50Hz or 60Hz)
Protection Input Circuit Breaker, Output Circuit Breaker, Electronic Circuits Instant Trp for Over Voltage, Over Load, Over Temperature, Short Circuit Protection and Alarm System
Envionment
Ambient Temp. 0°C ~ 45°C
Relative Hum. 0 ~ 90% Non-condensing
Altitude 1500 meter
Dimensions W x H x D (mm) 430x750x990 600x970x1240 800x1090x1600 800x600x1600
Net Weight (kg) 150 175 345 385 528 635 700 1000 1350 1620
AFC SERIES - SINGLE PHASE SPECIFICATIONS:
AFC SERIES - THREE PHASE SPECIFICATIONS:
FREQUENCY CONVERTERS
1PHASE&3PHASE