Specifications
46
Model** 0100 0125 0150 0200 0250 0300 0350 0400 0500 0600 0800 1000 1250 1500
Capacity (kVA)
100 125 150 200 250 300 350 400 500 600 800 1000 1250 1500
Circuit Type Inductive Voltage Regulator
Input
Phase 3P3W / 3P4W
Voltage Range* -13% - +17% (option: -22% - +30%)
Frequency 47Hz - 63Hz
Output
Phase 3P3W / 3P4W
Voltage 200V / 208V / 220V, 380V / 400V / 415V ± 2% (±1%-±5% adjustable)
Voltage Modulation < 4 V/s
Overload 125%-40min; 150%-20min; 175%-10min; 200%-5min
Total Harmonic
Distortion
< 1% (compared with input)
VA Efciency >97%
Measurement
Measurements Input line voltage and frequency, Output line voltage, Phase voltage, Line current and frequency,
VA, W, PF, Load rate, Internal temperature
Protection
Protection
Functions
Phase loss, phase reverse, output over voltage & under voltage, output overload, over temperature, over current,
redundant cicuit control. Event history log for 200 events.
UserInterface
Operation LCD and Push buttons
Alarm Alarm 1. Audio. Alarm 2. Activate
Communication RS-485
Software Remote control and monitor
Environment
Working
Temperature
-50C-400C
Storage
Temperature
-300C-500C
Humidity < 95% (non-condensing)
Altitude < 1000 meters
CoolingSystem
Type Fan cooling
Other
Noise < 60dB
Optional Auto transformer, full time lightning & surge protection, output on & off electromagnetic contactor
* Other input ranges on request
** Prec the model no. with APH-33 for the full part number.
Custom made specications on request
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specication or design can be changed at anytime without prior notice.
ELECTRONIC
INDUSTRIALINDUCTIVETYPE