EXTERNAL BATTERY SUPER CHARGER
DESCRIPTION:
The PHD external battery charger is suitable for any 192Vdc
and 240Vdc system (16 and 20 batteries in series). It is designed
for 192Vdc and 240Vdc UPS systems to enable longer standby
times for them. The 240Vdc version can be used with PHD’s T3
Series (6-10kVA models) and T4 Series (10-20kVA models) and the
192Vdc version can be used with PHD’s T3T Series (5-15kVA) and
T4T Series (10-15kVA). It is easy to install as it is connected
in parallel to the UPS’s existing battery charger.
Radiation IEC 61000-3-2
Safety IEC 60950-1/EN 60950-1
Drop, Variation ISTA Procedure 2A
MechanicalCharacteristics
Inlet, Outlet Terminal Block
Dimensions (W x D x H) (mm) 200 x 352 x 450 340 x 250 x 110
Net Weight (kg) 15 6
Model ST-CHARGER-10A ST-CHARGER-12A
Input
Voltage (176 -276)VAC @ Full Load
Frequency (46 - 75)Hz for 50Hz system
Power Factor ≥0.96@ full load
THD <20%@ full load
Output
Current 10A Nom. / 10A Max. 12A Nom. / 21A Max.
Voltage 160V Minimum, 218V Nominal, 224V Maximum 200V Minimum, 273V Nominal, 280V Maximum
Voltage Ripple 1%@ full load
Current Ripple 10% of Ah CAP @ full load
Efciency 90%
FaultProtection
Output Reverse Polarity Protection Fuse will open when reversing
Short-circuit Protection Yes
Input Protection 276Vac(+/- 2%) Over Voltage, 176 Vac(+/- 2%) Under Voltage, 110%,1s Open Circuit
FaultProtection
Working and Storage Temperature 00C - 400C
Humidity <95% (No condensing)
Altitude < 1000m
FaultProtection
ESD IEC 61000-4-2 Level 4
RS IEC 61000-4-3 Level 3
EFT IEC 61000-4-4 Level 4
Surge IEC 61000-4-5 Level 4
Conduction IEC/EN 62040-2 Category C3
FEATURES:
• Compact and light
• Easy to install
• Battery overcharge protection
• Input surge protection.
BATTERY CHARGER