Specifications
36
Model ES1948
Input
Voltage Wide Input Range: 90-275Vac or 310-480Vac
Frequency 44~66 Hz
Input Protection 13A HRC fuses at input of SMR(line and neutral);
power circuit is turned off if the AC voltage exceeds 275Vac or falls to less than 90Vac
Current <12A rms
Power Factor >0.99 at full load; sinusoidal wave shape
THD <5% at full load; satises requirements of EN61000-3-2
Efciency >91% at nominal mains voltage
Output
Voltage Float: -Adjustable 48~59V; Equalise: -Adjustable 50~61V
Current Limit Adjustable 5~40A
Power (Max) 1900W at 48~60Vdc(input>185Vac); 900W at 48~60Vdc(input 90~185Vac)
Load Sharing Better than ±5% of full scale with active current sharing from MCSU2048
Protection Overvoltage - only faulty unit shuts down
Overcurrent - can sustain short circuit at output terminals indenitely
Over-temperature - gradual reduction of current limit if heat-sink temperature exceeds pre-set limit
Static Regulation Line- +0.1%; Load- +1.0%
Dynamic Regulation +3% for 10~90% or 90~10% load variation; +1% for +25% step change in AC input voltage
Output Noise < 2mVrms Psophometric weighting; < 10mVrms 10kHz - 100MHz; < 100mV peak to peak 0~30MHz bandwidth
Other
Surge Protection EN 61000-4-5
EMC Emission: EN 61000-6-3,Immunity: EN61000-6-1
Inrush Current <12 Arms peak at nominal mains voltage
Voltage Withstand Test 3.0 kVac – input and output (4.25 kVdc primary-secondary); 1.5 kVac – input earth (2.12 kVdc
primary-ground); 0.75 kVdc – output earth
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specication or design can be changed at anytime without prior notice.
Environmental
Audible Noise @ 1m < 65dBA
Operating Temperature Operating range -40
0
C ~ 70
0
C; derated power at 50
0
C ~ 70
0
C
Cooling Two fan cooled, speed controlled and alarmed
Humidity 0~95% non-condensing
Mechanical
Dimension (W x H x D) 41mm x 144mm x 287mm
Weight <1.9kgs(4.19lbs)
Alarms
Alarm & Status LED
indication on SMR
On (Green) - SMR functioning normally
Alarm (Yellow) - Blinking when any SMR alarm is present.
Shutdown (Red) - Stays on when SMR has turned off due to a signal from the
MCSU2048 or an internal fault
Rectier Alarms Low/High output voltage alarm; Over voltage shutdown alarm; Current limit alarm; Fan Alarm;
Temperature alarm; Rectier failure alarm