Specifications
28
28
Model* ST2000-
3360
ST2000-
3380
ST2000-
33100
ST2000-
33120
ST2000-
33150
ST2000-
33200
InputRectier
Nominal Capacity - kVA 60 80 100 120 150 200
Input Nominal Voltage 200/208 V 3P or 380/400/415 V 3P + N or 440/465/480 V 3P
Nominal Frequency 50 / 60 Hz (Can be used as frequency converter)
Frequency Range + - 5%
P.F. @ 400V at Nominal 0,83 or 0,93 with Input Filter/PFC
Soft Start time 20-30 seconds
Battery 12Vdc x 32 = 384Vdc
Charge Current (Max) 20A 30A 40A 60A
InverterInput
Nominal Voltage 192 V for 200/208 V – 384 V for 380/480 V
InverterOutput
Nominal Voltage 200/208 V 3P or 380/400/415 V 3P + N or 440/465/480 V 3P
Current at p.f 0.8 86.71 115.6 144 174 221 287
Nominal Frequency 50/60 Hz
THD Linear load =<1,5%
THD at Non Linear load with Crest Factor 3:1 =<5%
Static Voltage Regulation + - 1%
Dynamic Voltage Regulation 0-100% + - 5%
OutputFrequencyRegulation
With Mains
Synchronisation (%)
+/- 1; 1,5 ;2,4
With Internal Micro + - 0,001%
Load Crest (Ipk/lrms) Better than 3 : 1
Overload 110% for 60 min -- 125% for 10 min -- 150% for 1 min
Efciency AC-AC @ 100% 93.4 93.5 94.1 95.1
MechanicalData
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specication or design can be changed at anytime without prior notice.
Dimensions (W x H x D) (mm) 800 x 750 x 1200 1400 x 750 x 1200
Weight (kg) 580 630 670 700 900 1100
UPS - ONLINE (TRANSFORMER)
3PHASEINPUT,3PHASEOUTPUT