Specifications

24
Model ST5
010
ST5
020
ST5
030
ST5
040
ST5
050
ST5
060
ST5
080
ST5
100
ST5
120
ST5
160
ST5
200
ST5
300
ST5
400
Input
Voltage * 380/400VAC ± 25%
Rectier Frequency
Range
40Hz~65Hz
SYNC Frequency
Tracking Range
50Hz ± 5% (± 10% option)
Phase 3φ4W+PE
Battery 12Vdc × 29 = 348Vdc / 12vDC x 30 = 360Vdc
Charge Current (Max) 5~40A (adjustable) 5~80A (adjustable)
Charge DC Voltage
Regulation
395V ± 5Vdc
DC Ripple Voltage <1%
Output
Capacity (kVA) 10 20 30 40 50 60 80 100 120 160 200 300 400
Power Factor 0.8
Phase 3φ4W+PE
Voltage * L-N: 220VAC ±1%, L-L: 380VAC ± 1%
Frequency Utility normal, follow in phase automatically, Utility fault, output frequency at 50Hz ± 0.2%
Parallel mode
(optional)
None-principle-subordinate Adaptive Control Technique, User can extend parallel capacity as needed
for N+1 parallel redundancy
3 phase 100% load
unbalance voltage
stability
≤2%, allows 100% unbalance
Waveform Sinewave THD ≤ 3% (linear load)
Crest Factor 3:1
Efciency 90%
Static Bypass
Transfer Time
0ms
Overload Capacity 110% load for 30 min,125% load for 10 min,150% load for 1min
Regulation no load to
full load steady state
±2%
Other
Panel Display LCD Display indicates 3 phase input voltage, input frequency, 3 phase output voltage, load, battery voltage,
battery charging and discharging etc. LED indicates running status
Battery Self-Testing Automatically sounds an alarm and estimates battery status in battery abnormal status
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specication or design can be changed at anytime without prior notice.
Lightning Protection Complies with IEC 1312
Operating Temp.,
Humidity
00C-400C, 95% (non-condensing)
Dimension
(W x D x H) (mm)
500 x 800 x 1180 800 x 800 x 1600 1000 x 800 x 1800 1800 x
1000 x
2000
2200 x 1000
x 2000
Weight (kg) 185 205 235 430 450 470 680 705 745 805 1400 2350 2380
UPS - ONLINE (TRANSFORMER)
3PHASEINPUT,3PHASEOUTPUT