Specifications

18
Model FP1600 FP2500 FP3200 FP6000
Topology True On-Line, Double Conversion
On-battery Waveform Pure Sine Wave
Input
Maximum Capacity (VA/W) 1600VA / 1120W 2500VA / 1750W 3200VA / 2240W 6000VA / 4200W
Nominal Input (Voltage Regulation) * 230VAC (160VAC-276VAC)
Nominal Input Frequency 50/60 ± 5Hz
Input PFC > 0.98 @ Full Load
Input Short Protection Circuit Breaker
Output
Nominal Output (Voltage Regulation) 208/220/230/240 VAC nominal (Rated Voltage ± 2%)
Output T.H.D < 3% @ Linear Load
High Efciency Mode (AC to AC) > 88% 90%
Crest Factor 3 : 1
Output Frequency 50 / 60Hz (Autotracking)
Overload Capability Sustaining 50sec @ 108% Load; 28sec @ 110-120% Load; 15sec @ 120-130% Load; 9sec
@ 140-145% Load; Immediate Response @ 150% Load
Battery(Extendiblein2UHigh
Modules)**
User Replaceable Battery 48V (1 x 48VDC
Battery Pack)
96V (2 x 48VDC
Battery Pack)
96V (2 x 48VDC
Battery Pack)
96V (2 x 48VDC Battery
Pack)
Typical Backup Time (Full / Half Load) 7 / 18 min 8 / 20 min 6 / 17 min 4 / 10 min
Battery Type Sealed VRLA 12V7Ah; Hot Swap
Recharge Time to 90% 8 hours 4 hours
AdvancedWarningDiagnostics
Front Panel Indication Front panel menu driven LCD monitoring and control panel for all functions
Audible Alarms DC Mode, Low battery, Voltage / Frequency Error, Charger Fail, High Temp,
Overload, Fault, PFC Overload
CommunicationInterface
Communication Port RS232 (Standard), DB9 or USB or AS400 or SNMP / HTTP (Optional), SNMP (Optional)
Environmental
Operation Temperature 0 ~ +40
0
C
Storage Temperature -15 ~ +50
0
C
Relative Humidity 0% - 95% non-condensing
Audible Noise < 45dBA @ 1 meter from surface of the unit
Mechanical
Dimensions (W x H x D mm) - Rack Position 426 x 88 x 500 426 x 176 x 500 426 x 88 x 500 426 x 176 x 500
Weight (UPS / Battery Packs) 12kg / 11.2kg 13.2kg / 31.2kg 13.4 / 31.4kg 16kg / 31.4kg
Conformance
EMI / RFI Compatibility EN50091-2 Class B, EN55022B
Safety Certications CE, TUV / GS
* 10V systems available on request
** Each battery module comprises 2 x 48VDC battery packs in a 2U box.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specication or design can be changed at anytime without prior notice.
UPS - ONLINE (TRANSFORMERLESS)
1PHASEINPUT,1PHASEOUTPUT