Specifications
16
16
Audible Alarms Battery Mode, Low Battery, Overload, Fault
CommunicationInterface
Communication Port RS232 (Standard), DB9 or USB or AS400 or SNMP / HTTP (Optional)
Environmental
Operation Temperature 0-400 C
Storage Temperature -150C to 500C
* All T3R models have a long standby option with no built in batteries, this is the charge current of the long standby models.
For long standby models, add “-L“ to the part number.
** 6 and 10kVA models can have up to 25A charging capabilities when connected in parallel with the ST-CHARGER external super charger.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specication or design can be changed at anytime without prior notice.
Model ST3R10 ST3R20 ST3R30 ST3R60 ST3R100
Topology
True On-Line, Double Conversion
Output Waveform
Pure Sine Wave
Input
Maximum Capacity (VA/W)**
1000VA/800W 2000VA/1600W 3000VA/2400W 6000VA/4800W 10000VA/8kW
Nominal Input Voltage
230 VAC
Input Regulation Voltage 160~300 VAC Single Phase w/ Ground 160~300 VAC Single Phase
w/ Ground
Nominal Input Frequency
50/60 ± 4Hz
Input PFC
≥0.95 ≥0.98
Input Short Protection Circuit Breaker
Output
Nominal Output Voltage 220/230/240 VAC nominal
Output Voltage Regulation ± 2%
Output T.H.D
≤3% (Linear Load)
≤6% (Non-Linear Load)
≤4% THD (Linear Load)
≤7% THD (Non-Linear Load)
≤2% THD (Linear Load)
≤6% THD (Non-Linear Load)
High Efciency Mode (AC to DC)
85% 85% 88% > 88%
High Efciency Mode (DC to AC)
83% 83% 83% > 88%
Crest Factor 3:1
Start on Battery Yes
Output Frequency 50 Hz ± 0.2 Hz 50 Hz ± 0.5 Hz
Battery
Typical Backup Time
9 minutes 12 minutes 8 minutes 10 minuts 8 minutes
Battery Type Sealed Lead-Acid maintenance-free 12VDC/7Ah per cell
12VDC/9Ah per cell
Number of Batteries 3 cells 8 cells
20 cells
Recharge Time to 90% 5 hours
7 hours 8 hours
Charge Current of Long Standby Model * 8A 4.2A **
AdvancedDiagnostics
Front Panel Indication – LCD UPS Status, I/P Voltage & Frequency, O/P Voltage & Frequency,
Battery Voltage, Battery Capacity, Loading %, Temperature, History Alarm.
Front Panel Indication – LED Normal (Green), Warning (Yellow), Fault (Red)
Relative Humidity 20% to 90% non-condensing
Audible Noise
< 45 dBA @ 1 meter < 50 dBA @ 1 meter < 55 dBA @ 1 meter
Mechanical
Dimensions (W x H x D mm)
440 x 88 x 465
(with internal batteries)
440 x 88 x 465 (UPS only)
440 x 88 x 465 (External Battery)
440 x 132 x 640 (UPS Only)
440 x 132 x 640 (External Battery)
Weight (Net Weight with Batteries) (kgs)
15.5 35 36 85 88
UPS - ONLINE (TRANSFORMERLESS)
1PHASEINPUT,1PHASEOUTPUT