Model ST3010 ST3020 ST3030 ST3060 ST3100
Topology True On-Line, Double Conversion
On-battery Waveform Pure Sine Wave
Input
Maximum Capacity (VA/W) 1000VA/800W 2000VA/1600W 3000VA/2400W 6000VA/4800W 10000VA/8000W
Nominal Input 230VAC
Input Voltage Regulation 160~300 VAC Single Phase w/ Ground 170~285 VAC Single Phase
w/Ground
Nominal Input Frequency 50/60 ± 4Hz
Input PFC ≥0.95 ≥0.98
Input Short Protection Circuit Breaker
Output
Nominal Output 220/230/240 VAC nominal
Output Regulation ± 2% ± 1%
Output T.H.D ≤3% (Linear Load)
≤6% (Non-Linear Load)
≤4% THD (Linear Load)
≤7% THD (Non-Linear Load)
≤2% THD (Linear Load)
≤6% THD (Non-Linear Load)
High Efciency Mode (AC to DC) 85% 85% 88% > 88%
High Efciency Mode (DC to AC) 83% 83% 83% > 88%
Crest Factor 3:1
Start on Battery Yes
Output Frequency 50 Hz ± 0.2 Hz 50 Hz ± 0.5 Hz
Battery
Typical Backup Time (at full load) 9 minutes 12 minutes 8 minutes 10 minutes 8 minutes
Battery Type Sealed Lead-Acid maintenance-free 12VDC/7Ah per cell 12VDC/9Ah per
cell
Number of Batteries 3 cells 8 cells 20 cells
Recharge Time to 90% 5 hours 7 hours 8 hours
Charge Current of Long Standby
Model *
8A 4.2A **
AdvancedWarning
Diagnostics
Front Panel Indication – LCD UPS Status, I/P Voltage & Frequency, O/P Voltage & Frequency,
Battery Voltage, Battery Capacity, Loading %, Temperature, History Alarm.
Front Panel Indication – LED Normal (Green), Warning (Yellow), Fault (Red)
Audible Alarms Battery Mode, Low Battery, Overload, Fault
Communication
Interface
Communication Port RS232 (Standard), DB9 or USB or AS400 or SNMP / HTTP (Optional)
Environmental
Audible Noise < 45dBA @1 meter < 50dBA @1 meter < 55dBA @1 meter
Mechanical
Dimensions (W x H x D mm) 160 x 220 x 400 200 x 352 x 450 260 x 717 x 570
Weight (Net Weight with Battery) (kgs) 15 34 35 90 93
UPS - ONLINE (TRANSFORMERLESS)
1PHASEINPUT,1PHASEOUTPUT