Specifications
12
* All T3 models have a long standby option with no built in batteries, this is the charge current of the long standby models.
For long standby models, add “-L“ to the part number.
** 6 and 10kVA models can have up to 25A charging capabilities when connected in parallel with the ST-CHARGER external
super charger.
All information contained in this brochure is purely indicative and can not be used to form any contractual obligations.
Specication or design can be changed at anytime without prior notice.
Model ST3010 ST3020 ST3030 ST3060 ST3100
Topology True On-Line, Double Conversion
On-battery Waveform Pure Sine Wave
Input
Maximum Capacity (VA/W) 1000VA/800W 2000VA/1600W 3000VA/2400W 6000VA/4800W 10000VA/8000W
Nominal Input 230VAC
Input Voltage Regulation 160~300 VAC Single Phase w/ Ground 170~285 VAC Single Phase
w/Ground
Nominal Input Frequency 50/60 ± 4Hz
Input PFC ≥0.95 ≥0.98
Input Short Protection Circuit Breaker
Output
Nominal Output 220/230/240 VAC nominal
Output Regulation ± 2% ± 1%
Output T.H.D ≤3% (Linear Load)
≤6% (Non-Linear Load)
≤4% THD (Linear Load)
≤7% THD (Non-Linear Load)
≤2% THD (Linear Load)
≤6% THD (Non-Linear Load)
High Efciency Mode (AC to DC) 85% 85% 88% > 88%
High Efciency Mode (DC to AC) 83% 83% 83% > 88%
Crest Factor 3:1
Start on Battery Yes
Output Frequency 50 Hz ± 0.2 Hz 50 Hz ± 0.5 Hz
Battery
Typical Backup Time (at full load) 9 minutes 12 minutes 8 minutes 10 minutes 8 minutes
Battery Type Sealed Lead-Acid maintenance-free 12VDC/7Ah per cell 12VDC/9Ah per
cell
Number of Batteries 3 cells 8 cells 20 cells
Recharge Time to 90% 5 hours 7 hours 8 hours
Charge Current of Long Standby
Model *
8A 4.2A **
AdvancedWarning
Diagnostics
Front Panel Indication – LCD UPS Status, I/P Voltage & Frequency, O/P Voltage & Frequency,
Battery Voltage, Battery Capacity, Loading %, Temperature, History Alarm.
Front Panel Indication – LED Normal (Green), Warning (Yellow), Fault (Red)
Audible Alarms Battery Mode, Low Battery, Overload, Fault
Communication
Interface
Communication Port RS232 (Standard), DB9 or USB or AS400 or SNMP / HTTP (Optional)
Environmental
Audible Noise < 45dBA @1 meter < 50dBA @1 meter < 55dBA @1 meter
Mechanical
Dimensions (W x H x D mm) 160 x 220 x 400 200 x 352 x 450 260 x 717 x 570
Weight (Net Weight with Battery) (kgs) 15 34 35 90 93
UPS - ONLINE (TRANSFORMERLESS)
1PHASEINPUT,1PHASEOUTPUT