Specifications
10
A Positive DC connector
B Negative DC connector
C Cooling Fan
D AC Output Fuse
E AC Output Terminal Block
F Solar Panel Input.
Model ST2008X ST2010X ST2020X ST2040X ST2060X ST2080X
Capacity Watt/Amps 800W/3.6A 1600W/7.2A 2400W/10.9A 4000W/18.1A 6000W/27.2A 8000W/36.3A
Input
Normal
Voltage
220Vac / 110Vac 220Vac
Acceptable Voltage 120-275Vac / 60-135Vac 120Vac-275Vac
Frequency 50Hz / 60Hz (45Hz- 70Hz)
Voltage
Range
Line Low Transfer 120Vac +-2% /60VAC +- 2% 120Vac+-2%
Line Low Return 130Vac +-2% /65Vac +-2% 130Vac+-2%
Line High Transfer 275Vac +-2% / 135Vac +-2% 275Vac+-2%
Line High Return 260Vac+-2% / 130Vac +-2% 260Vac+-2%
Output Voltage
220Vac (230V or 240 Vac re-settable via LCD panel);
110Vac (115V or 120Vac re-settable via LCD panel)
230Vac (220V
or 240Vac
re-settable via
LCD panel)
VoltageRegulation
(BattMode)
<3% RMS for entire battery voltage range
Frequency
50Hz or 60 Hz
FrequencyRegulation
(BattMode)
+-0.1 Hz
PowerFactor
0.67 0.6 0.62
Waveform
Pure Sinewave
Transfer
Time
Typical
< 8ms
Battery
BatteryVoltage
12Vdc 24Vdc 48Vdc
BackupTime(atfullload)
Long time available
MaxChargingCurrent
(3stepsselectable)
>40A >50A >60A
Solar
Power
SolarPowerServer50A
(Option)
Optional* Standard
Display
LCD
LCDExtendedLCD
RemoteControl(optional)
UPS status,I/P &O/P Voltage Frequency, Load%, Battery Voltage & %, Temperature, Model
LED
Normal (Green), Warning (Yellow), Fault (Red)
Audible
Alarm
BatteryMode
Beeping every 4 seconds
LowBattery
Beeping every second
UPSFault
Beeping Continuously
Overload
Beeping twice per second. UPS will shutdown automatically in 30 seconds if overload is over
105~ 150% and up to 150 % will shutdown immediately.
OperationTemperature
0-40 degree C; 32-104 degree F
Environ-
ment
RelativeHumidity
0-95% non-condensing
AudibleNoise
Less than 55dBA (at 1M)
Physical
NetWeight(Kgs)
14 21 23 49.2 51.4 53.6
Dimension(WxHxD)mm
RackMount
440*132*290 440*132*360 440*132*360 N/A N/A N/A
WallMounted(W*H*D)mm
298*400*150 298*450*190 298*450*190 415*600*260 415*600*260 415*600*260
* Add “S“ to the part number for the solar server option
Different specications required are available
All specications mentioned above are subject to change without prior notice.
UPS - LINE INTERACTIVE
PURESINEWAVE[LongStandby]