Analogue Addressable Fire Panels FP1500 Manual for Installation, Configuration and Commissioning Version 2.
Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea © 2003 GE Interlogix B.V.. All rights reserved. GE Interlogix B.V. grants the right to reprint this manual for internal use only. GE Interlogix B.V. reserves the right to change information without notice.
CONTENTS 1 Introduction............................................................................................................................................ 3 1.1 Contents of the package ............................................................................................................... 3 1.2 Glossary of symbols...................................................................................................................... 4 1.3 The FP1500 analogue system ............................
5.4.6 5.4.7 5.4.8 Supply faults ................................................................................................................ 46 Low battery .................................................................................................................. 46 Others .......................................................................................................................... 46 6 Maintenance.....................................................................................
1 INTRODUCTION The FP1500 Aritech analogue addressable fire detection system has been designed and manufactured in compliance with EN54-2:1997 and EN54-4:1997 and has approvals pending. Specialized staff with experience in manipulating and connecting electric and electronic devices must perform the installation of the system. The installation should comply with the guidelines and requirements of EN54-14 and any other applicable local authority laws or requirements.
1.2 Glossary of symbols The symbols listed below appear throughout this manual to make it easier to understand and as a reminder of important warnings and notes. Ground connection: For your safety and protection of the system, it is required to make this connection and ensure that is always correct. Electronic equipment sensitive to electrostatic discharges: When working with the electronic circuits, always wear an anti-static bracelet.
Figure 2.
• Disconnect the mains (110 VAC or 230 VAC) and the batteries before connecting or disconnecting any of the internal circuits of the fire panel. • The proper way of supplying current to the panel is: First connect the mains magneto-thermal switch (110 VAC or 230 VAC), and then connect the batteries. Not following this procedure may cause a small discharge and damage the system.
2 THE FP1500 ANALOGUE FIRE PANEL 2.1 Description of the control panel This section provides a visual diagram of the control panel keyboard and of the main board connectors in order to facilitate the identification of each of the components of the fire panel. Figure 3. FP1500 Analogue addressable fire panels 1 23 2 4 16 10 17 5 6 7 11 12 19 20 8 9 24 18 13 14 21 22 15 FP1500 Installation, Configuration and Commissioning Manual 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19.
Figure 4. FP1500 main electronic board and connectors 6 10 11 12 13 14 4 3 5 1 7 2 16 8 9 15 1. Mains connector * 10. Potential-free relays connector 2. Transformer 3. Main electronic board 11. Supervised sounders and auxiliary 24 VDC connectors 4. Display contrast adjustment potentiometer 12. RS485 connector 5. Auxiliary 24 VDC fuse * 13. RS232 connector 6. RS485 IC socket 7. Mains Input fuse * 14. Loop connector: FP1500/1 has only 1 where the FP1500/2 has 2 8.
available at this level. The installer may add and remove sensors, control events, print, etc. To access the connectors and main electronic parts of the fire panel, a screwdriver is required. Level 4: This level is reserved for the manufacturer's staff i.e. GE Aritech personnel. Changes in the operation of the fire panel may be performed and special tools and software are necessary. 2.3 Features and functions The FP1500 series share features and functions within the two models, FP1501 and FP1502.
3 INSTALLATION OF THE SYSTEM This chapter describes the installation process step by step, from fixing the fire panel to the wall to connecting each of the possible components of the system. Follow each of the listed procedures carefully. 3.1 Installation tools For installation: A flat screwdriver for connectors and a Phillips screwdriver for the star-headed screws of the front casing, wire-stripping pliers and, multi-meter (tester) is required.
3.2 Panel positioning For optimum operation and maintenance of the fire panel, several factors must be kept in mind when deciding on the installation position. The location must be protected by the fire detection system. Temperature should be controlled between 5 and 40º C and the relative humidity must not exceed 95% (without any condensation). The location must be sheltered to avoid possible jolts or vibrations and away from cable runs that could cause interference in the communications. 3.
3.5 Electrical connections and cables The fire panel must be connected to the mains through an external bipolar magneto-thermal switch. The mains cable must have a minimum section of 1.5 mm² and the voltage must be 110 VAC or 230 VAC. To avoid potential short-circuits and electromagnetic interference the mains cable must be kept away from the loop connection cables and from the communication ports. To protect the connections, the use of PG11-type cable adapters or seals is recommended.
For your safety, the order in which the power is reconnected must be: Mains first, then the batteries. Do not connect the fire panel to the mains until you have completed the commissioning procedure (See chapter 5). Connect the mains on the outside of the cabinet and with an adequate earth connection. The earth cable should be the longer of the three cables. Figure 7. FP1500 mains connection X 110 VAC Y 230 VAC 1. Mains fuse 2. Mains fuse 3. Neutral 4.
BLACK CABLE + RED CABLE BATTERY 12V 7 A/h BRIDGE CABLE (BLACK) 3.5.2 Connections on the main electronic board Figure 9. FP1500 main board connectors RS232 3.5.3 NA NC C NA NC C RELAY2 RELAY1 LOOP 1 R+ R- LOOP 2 RS485 R+ R- 1 + 1 O+ O- + RTS RXB TXA 1 B A B A + O+ O- 24VDC AUX SND 2 SND 1 Connecting a loop The loop structure is a closed (Class A) circuit. All the elements are connected to two wires that exit from the fire panel and return back to the fire panel again.
• Connect the output wires to points O+ and O- and the return wires to R+ and R-. The colouring of the cables helps to distinguish between (+) and (-). • Connect the ground cable or shield to the ground terminal. Be careful to connect only one of the ends, either the output (O) or the return (R) one. It is important to have continuity in the shield at each of the connections of the loop.
Each connection of the loop must give continuity to the shield. The loop ground connection R+ R- O+ O- End of shield well protected If necessary, the fire panel has an auxiliary 24 VDC output. It allows powering of additional elements that cannot be powered from the loop. It is also possible to connect such elements to an independent power supply. 3.5.4 Connecting sensors The analogue addressable sensors are the elements of the system that gather the information.
All sensors must be installed in clean environments. During construction and refurbishing work, they must be protected to keep them from being damaged and/or contaminated. When you have identified the detector type that better fit the protection need, the installation process can start. Installation is the same for any kind of sensor: PG700 Portable unit for all types • Install the connection base DB304 (See Instruction Manual). • Once base DB304 is installed, connect it to the loop.
Figure 11. Additional power supply 24 V power supply line from the fire panel Output auxiliary 24 VDC External power supply 3.5.6 Connecting sounders The FP1500 has 2 sounder outputs internally, identified as SND1 and SND2. On each of these outputs, supervised sirens may be connected with a total consumption of 300 mA. The installation and connection procedures are as follows: 1. Install the cable connecting any polarized siren (or with a corresponding diode) as required (without exceeding 300 mA). 2.
3.5.7 Connecting relays Relays outputs can be connected to the corresponding sockets on the main board (the ones furthest to the left). It is important to ensure that the terminals are tightly fixed. Figure 13. Connection of relays on the main board RELAY1 NA NC C NA NC C RELAY2 The relay output has three terminals: C: common NA: normally open NC: normally closed The EN54 standard requires a normally activated (fail-to-safe) fault relay. One of these relays may be used for this function (See section 4.
2. Check that the PINS on the IC are in good condition and unbent 3. Insert the IC into the correct position in the slot 4. Ensure the correct position of all the pins on the IC FP1500 Installation, Configuration and Commissioning Manual KAL 785/701 Slot on main board for KA785/701 chip The chip has an installation position. Check position.
4 SYSTEM CONFIGURATION The basic configuration of the system can be performed completely from the control unit. However, if an external PC is available, the process is made easier.
Figure 14. FP1500 keypad 4.1.1 General parameters The alphanumeric LCD screen of the FP1500 has 4 lines of information of 40 characters each. [Screen title]: this reminds you at all times of the current screen. [#Exit]: the <#> key takes you back to the previous menu Index of menu actions: Numbered in accordance with the number of options. Key in the number allocated to each action. Screen title Return to menu [MAIN MENU] [# Exit] 1. Configure 4. Connect 2. Test. 5. Disconnect 3. Time 6. Print 7.
checked. An alert is given if the detector is out of its calibration limits or if it is close to the prealarm margin. Choose a time of the day when the environment is usually in normal conditions. By default, the control unit proposes 00:00 hours. LED Flashing: All the elements of the loop send information or are consulted by the control unit regularly. Every time information is sent, the corresponding LED flashes. You can activate or deactivate the LED light; it is recommendable to leave it on [YES].
In option 1 select: Day / Month / Year [DD/MM/YYYY] In option 2
If more detailed information is required about the type and address of each device of the loop, select option 2 (See section 4.1.5.). From this point on, the configuration can be carried out using the software (external PC) or continued with the fire panel menu. 4.1.4 Configuring a zone [SYSTEM] 1. Loop 1 2. Loop 2 3. Loop 3 1 [# Exit] 7. Sirens 8. Relays 9. PC 4. Loop 4 5. Loop 5 6. Peripherals [Loop 1] 1. Zones 2. Elements 3. Auto-search [# Exit] 4. Calibrate 5. Prog. Dir.
4.1.5 Configuring elements [CONFIGURE] 1 2 [# Exit] 1. System 2. See Config. 3. Time/Date 4. System Op. 5. Check Prog. 6. Power Supply [SYSTEM] 1. Loop 1 2. Loop 2 3. Loop 3 4. Loop 4 5. Loop 5 6. Peripherals [Loop 1] 1. Zones 2. Elements 3. Auto-search 7. Events 8. Day Mode 9. Codes [# Exit] 7. Sirens 8. Relays 9. PC [# Exit] 4. Calibrate 5. Prog. Dir. Begin inspection at address [001] Loop: 01 Zone: 001 Address: 001 Text: Room 1005 Type: Ionic Analog.
Element 001 is called [Write the name of the element] [Upper Case Letters and Numbers] Select the option you wish to change or go back to continue with the other addresses. Introduction and change of the location text Element 001 is called [Room 87- ] [Lower case letters and numbers] Element 001 is called [PL.2 _ [Word 1] ] 0=Zone 1=Floor 2=Room 3=Corridor 4=Cupboard 5=Floor Element 001 is called [PL.
will use during the day period (e.g. 6:30 to 17:45). To change the alarm threshold to 65, simply change the value. When introducing the new value, the programme asks for the alternative value for the pre-alarm threshold. To change it to 50, simply introduce the new value. The pre-alarm threshold value must be lower than the alarm threshold otherwise the control unit readjusts the input value automatically. Loop: 01 Zone: 001 Address: 026 Text: Room 1005 Type: Thermal Analog.
7 [SYSTEM] [# Exit] 1. Loop 1 4. Loop 4 7. Sirens 2. Loop 2 3. Loop 3 5. Loop 5 6. Peripherals 8. Relays 9. PC SIREN 1 Logic event [003] Events-1 [000] Events-2 [000] LOGIC EVENT 1 ZONE MODE [001] TO [012] [YES] b) NO: The output is not activated if a fire is detected in the allocated zones (e.g. from 1 to 12). LOGIC EVENT 1 ZONE MODE [001] TO [012] [NO] 40 logic events can be defined. From the configuration menu, access system and from there select option 7 .
etc. After the allocated time, the siren changes to a continuous sound if one or more sensors are in alarm. This is only applicable to main board outputs (SND1 and SND2) and loop sirens. LOGIC EVENT 1 ZONE [001] TO [012] 1 / 2 Sensors [NO / YES -> YES 120 sec] LOGIC EVENT 1 ZONE 1 / 2 Sensors [001] TO [012][PULSING NO / YES -> YES 120 sec] 1/2 sensors No / Yes > Yes 000 sec.
1 [EVENTS] In option 1 allocate a number to the (e.g. [004]). [# Exit] 1. General 2. Logical Fault Event : [004] Pre-Alarm Event : [000] Recognised Event : [000] [CONFIGURE] 1 8 [# Exit] 1. System 4. System Op. 2. See Config. 5. Check Prog. 8. Day Mode 3. Time/Date 6. Power Supply 9. Codes 4. Loop 4 7. Sirens [SYSTEM] 7. Events [# Exit] 1. Loop 1 2. Loop 2 5. Loop 5 8. Relays 3. Loop 3 6. Peripherals 9.
ZONE [001] TO [012] 4.2.2 With Alert 1, the control unit warns of an alarm situation. The operator must press before the Alert 1 time, otherwise the full alarm is generated. If the control unit is on Received within the time, Alert 2 begins. Alert 2 begins when Alert 1 is triggered. For this reason, Alarm 2 must be adjusted to a time longer than Alert 1, to give the user time to investigate the cause of the alarm and take the appropriate decisions.
4.2.3 Configuration of the network The FP1500 allows the interconnection of up to 10 control units and/or repeaters on a network. The connection of control units is made through the RS485 serial port on the main board. Figure 15. Connection for RS485 The cable must be connected on the A and B terminals of each of the control units on the network. (See section 3.5.1) To avoid communication problems, you must install a 150-Ohm / ¼ W resistor on the first and last control units. Maximum 1.
1 [CONFIGURE] 1. System 4. System Op. 2. See Config. 5. Check Prog. 3. Time/Date 6. Power Supply [# Exit] 7. Events 8. Day Mode 9. Codes Once all the control units have been identified, one of them must be defined as the Master together with the mode in which they are to communicate. [SYSTEM] 1. Loop 1 2. Loop 2 3. Loop 3 [# Exit] 7. Loop 7 8. Loop 8 9. Loop 91 For this, from the [Configure] menu, access option 1 [System] and, from there, option 6 [Peripherals].
configuration of the address and the language is made through micro-switches on the bottom of the main board of the repeater. ADDRESS LANGUAGE These are the combinations for defining the address and language: Combinations for defining the address and language of the FP1500R repeaters SPANISH ITALIAN PORTUGUESE ENGLISH Once the address has been set, perform the auto-search for peripherals from the master control unit to configure all the elements installed on the network through the RS485 port.
TXA RXB A B 6 2 9 RXB TXA RS1 Before starting the installation of the modem, check that no element is connected to the RS232 port, which is to be used for this function. 6 [MAIN MENU] [# Exit] 1. Configure 4. Connect 2. Test. 3. Time 5. Disconnect 6. Print 7. See [PRINT] From the [Main Menu] screen, select option 6 select option 5 check that the internal printer is on [NO] mode. [# Exit] 1. Element 4. Disconnected 2. Historic 3. Mode 5.
1 [GSM] [#Exit] 1. Options 2. Status 3 Serial Port [ ] Activate MODEM: [ ] Fault Max.: [ ] SMS messages: [ ] Telephone PIN: [ 0000 ] [MODEM] [#Exit] 1. GSM 2. Normal 3. Telephones [TELEPHONES] 1: • Serial port: select the port where the modem is connected. • Activate modem: [NO] • Activate SMS: [YES] • PIN code: introduce the PIN number of the GSM SIM card. • Fault Maximum: this option enables the selection of the maximum number of alerts produced by faults. 4.
baud, 8 data bits, 1 stop bit without parity.
[Serial Port: Activate Modem: 3. If you use the configuration software, this option must be disabled, for the graphics software, it should be enabled. [01] [YES] To establish the communication of the control unit with the configuration software, the control unit must be in the [System menu] option 9 < PC > To ensure correct working, the configuration software must be version 2.0 or higher. 4.2.
For other applications using an ethernet network, contact your supplier. 4.2.7 Changing the firmware version When the version of the firmware is changed, the control panel clears the existing site configuration. To keep the configuration, download it to a PC with the configuration software In the FP1500 the change of the software version is made through the RS232 port with special software. If necessary, please contact your supplier. 4.2.
• Hardware flow control (As an external printer, the EPSON LX300 is recommended) To configure the printer: 6 [MAIN MENU] 1. Configure 5 7. See From [Main Menu] select option 6 . The control unit enters the printing menu. [# Exit] In [PRINT] select option 5 [# Exit] 4. Connect 2. Test. 5. Disconnect 3. Time 6. Print [PRINT] 1. Element 4. Disconnect 2. Historic. 5. Options 3. Mode Select whether the printer is external or internal.
LEVEL CODES: [2] From [01] to [01] Value: [ Duration: [05] Minutes LEVEL CODES: [3] LEVEL CODES: [3] Current Code: [0000] New Code: [0000] ] Press: The panel will indicates on what code number (between 01 and 10) the code is allocated. Write a 4-digit access code. E.g. From [01] to [05] : [1234] In this way, we only have 5 codes to allocate, since the first five have the access code [1234] If all ten codes are required: From [01] to [01] : [1111] From [02] to [02] : [2222]... etc.
5 COMMISSIONING OF THE SYSTEM Finally, the analogue detection system has been installed. Before powering it up, you must check the control unit works correctly. Follow all the steps set forth in this chapter. 5.1 Checking the system Before supplying power to the control unit, check all the following points. • Check that the control unit has been correctly mounted (See section 3.3). • Check the loops, ensuring that there is no cut or short circuit. Use the tester to check the continuity of the line.
• The general parameters are adjusted Choose language (See section 4.1) Standby and General Fault Message (See section 4.1.1) Adjust Time and Date (See section 4.1.2) • Configure loops (See section 4.1.3) Auto-search (See section 4.1.3) From the external PC, configuration software: (If you do not have a computer, it can also be configured through the control unit panel) • Editing of Zone (See section 4.1.4) • Editing of Texts (See section 4.1.5) • Editing of logic lines (See section 4.1.
• Disconnect half the installation and perform the auto-search. If the control unit functions correctly, the problem is to be found in the other half. If it does not function correctly, the problem is to be found on this section and you should shorten the installation until you find the point of conflict. Open circuit or short circuit fault in the loop: During the cabling of the loop and/or the installation of sensors, there may be an open or short circuit fault.
5.4.5 Out of service The LED on the front of the control unit displays “Out of service”. This warning is given when there is a lack of power supply and the voltage of the batteries, after a prolonged period of functioning, drops below a certain level (22 V), which does not guarantee the correct functioning of the control unit. To solve the problem you can: • Change the batteries • Get power supply It is recommended you disconnect the system if you cannot find an immediate solution. 5.4.
6 MAINTENANCE Fault repair and maintenance must be carried out by qualified personnel only. Adopt the maintenance measures recommended in EN54-14 and any other applicable local authority laws and requirements. Daily Maintenance: 1. The control unit must indicate normal functioning. Otherwise, the faults must be noted down in the register book and the maintenance company called. 2. Check that any previously noted fault has been corrected. Monthly Maintenance: 1.
Batteries: Even though the batteries test OK, it is recommended they be changed every four years.
Replacing components All the components used in this control unit have been chosen to obtain a highly reliable and long-lasting product. However, the manufacturers of the products referred to below indicate that their expected lifespan is below 15 years and they may therefore need to be replaced in the future.
7 TECHNICAL SPECIFICATIONS Mechanical specifications: Enclosure 420 mm x 335 mm x 110 mm 6.2 Kg without batteries 10 x 20 mm top; 10 x 20 mm inside. Cable input holes: Environmental: Temperature: Relative Humidity: Protection index Supports conditions: -5°C to +40°C 95% maximum without condensation. IP30 3K5 of the CEI 721-3-3:1978 Loop outputs: FP1500/1: FP1500/2: Maximum loop capacity.
Auxiliary 24 V output: Recommended cable: Serial ports: Number of serial ports: RS232 RS485 Recommended cable: Power supply Mains voltage: Voltage tolerance: Power supply input: 2 Port 1 RS232 Port 2 RS485 (optional). Galvanic isolation Maximum Length 15m Baud rate: 9600 Baud Recommended cable 3-wire cable 1 mm² stranded and shielded Maximum Length: 1200m Recommended cable 1.5 mm² stranded cable, screening recommended Baud rate: 9600 Baud End-of-line resistances: 150 ohm. KAL21A: 2 wire cable 1.
Batteries: Alphanumeric screen: Number of alarm zones per control unit: 2 units of 12 VDC 7 A/h (lead type) LCD screen 4 lines x 40 characters with back lighting FP1500/1 & /2: 20 zones with LED alarm indicator 20 zones with LED fault / disable indicator Access codes: Level 2: Level 3: 10 user-definable codes (factory setting of 0000). Code 9898.
8 APPLICABLE STANDARDS The FP1500 has been designed according to the EN54-2:1997 and EN544:1997 and EN60950 / A4+A11 (1997) standards. EN54-2 has basic and optional requirements. Optional requirements of the EN54-2:1997: SUBJECT Indication Controls Outputs SECTIONS 8.4 7.12 7.11 9.5 10 7.
9 APPENDIX: ADDRESSES OF MODULES ON 1 2 ON ON 3 4 5 6 7 8 1 2 3 ON 3 4 5 6 7 8 3 4 5 1 2 3 4 4 5 6 7 8 1 2 3 4 6 7 8 1 2 5 7 8 3 1 2 4 5 6 7 8 1 2 4 3 4 4 5 6 7 8 1 2 3 4 4 5 6 7 8 7 8 5 5 3 4 5 1 2 4 5 6 7 8 1 2 6 7 8 4 5 3 4 5 4 5 6 7 8 6 7 8 1 2 5 6 7 8 1 2 6 7 8 3 4 5 4 5 6 7 8 6 7 8 4 5 1 2 5 6 7 8 1 2 5 6 7 8 1 2 1 2 6 7 8 1 2 4 5 4 5 6 7 8 4 5 7 8 1 2 4 5 7 8
ON 1 2 3 ON 4 5 6 7 8 1 2 3 1 2 3 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 208 209 210 ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 214 215 216 1 2 3 ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 220 221 222 ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 226 227 228 1 2 3 ON 4 5 6 7 8 ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 231 232 233 234 ON ON ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 237 238 239 240 ON ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 243 244 245 246