Specifications

60
© 2012 Emerson Climate Technologies, Inc.
Printed in the U.S.A.
AE8-1368 R2
Figure 7.4 – 4D Terminal Box Connections
6. Install the terminal box on the compressor by
routing the harness leads through the provided
opening in the bottom of the box. Secure to the
compressor using the four anchor screws.
7. Secure the wiring harness assembly to the
terminal box by installing two screws.
8. Inside the terminal box:
Connect compressor power terminal lugs
Connect wires to the sensor module including:
- voltage sensing leads
- crankcase heater output
- communication cable (to control module)
- 24VAC power output (to control module)
9. Reconnect the RS-485 communications plug.
10. Reconnect the harness to the oil pressure sensor.
11. Replace the terminal box cover and secure with
two screws.
12. Reinstall the side cover over the pressure controls.
13. Reinstall the control module access cover and
secure with two screws.
14. Apply power to the compressor and CoreSense
Diagnostics
modules.
11.0 Removal of the Compressor (4D)
1. Turn off power to the compressor, crankcase
heater, and CoreSense Diagnostics modules.
2. Isolate the compressor and evacuate per accepted
industry practice.
3. Inside the terminal box
• Remove compressor power terminal lugs
Figure 7.3
4D CoreSense Diagnostics v2.11 Assembly Reference Drawing