Current Overload Trip
This fault is a result of continuous compressor current that exceeds the configuration (MCC) limit by 10% for 60
seconds as determined by the current sensing transducer. This is independent of the compressor protector or
motor temperature sensors.
The comp will auto-reset after 2 minutes (plus any remaining anti-short cycle time).
The MCC (maximum continuous current)
may be edited through the E2 setup screen
for each compressor
6.30
Graph the
amperage
preceding the fault
Is the compressor current in the
graph lower than the published
MCC value for this compressor,
voltage and refrigeratnt?
Troubleshoot for high
current. Verify that the
CT reads the correct
amperage. Replace the
CT if necessary
Look in the setup
tab for this
compressor to
determine the
MCC trip point
Did the compressor trip
at a current level less
than shown in the setup
tab?
Refer to section 4.x and
read back the MCC value
for this control module.
Re-load the value if it has
changed from the
published (RLA x 1.4)
MCC value
If the MCC value shown
on the setup tab is less
than the published MCC
value for this compressor,
voltage and refrigerant,
reload the MCC value per
section 4.x instructions
Yes
No
Yes
No