Specifications
28
© 2012 Emerson Climate Technologies, Inc.
Printed in the U.S.A.
AE8-1368 R2
Module Low Voltage Trip
Sensor Module input voltage
must be greater than 16.5 volts
Check the Sensor Module supply voltage
at the leads connected to the terminal
labeld “24 VAC IN” in the terminal box.
Is the voltage below 16.5 volts?
Normal Operation. Check the supply voltage at the
transformer. Correct the low voltage condition.
Voltage must be above 16.5 V for module to reset.
Verify proper transformer VA rating and wiring size
(See Appendix C). Replace the transform if
necessary.
Yes
No
6.8
Reonnect the sensor module power
leads. Check the voltage on pins 4 and
15 of the 18-pin AMP connector to the
control module. Is the voltage below 16.5
V?
Check the white plug connector at the sensor
module and be sure that it is completely
engaged. If movement of the connector
causes intermittent power, resize the
receptacle pins or replace the harness
Check the continuity of the wires in the
cable harness from pins 4 and 15 of
the 18-pin AMP connector. Do the
readings indicate a poor connection or
a broken wire? (See Appendix B)
Yes
No
Note: The 24VAC supply voltage to the control module
is also used to provide power to the unloader coil(s) if
present. In the event of intermittent low voltage trips it
may be helpful to check the transformer output voltage
while overriding the unloader coil ON with the rack
controller. This can be done by forcing the unloader
stage “OFF”.
If powering the unloader coil(s) causes the supply power to
the module to drop below 16.5 v, check to be certain that
the transformer meets the proper VA requirements. Refer
to Appendix C of this manual for information concerning
proper transformer selection.
White Power Connector At
Sensor Module










