User Guide

7
Programming
The AV unit can be programmed on site by using the option switches fitted to the unit.
SW1
No Option ON OFF
1 Input Type Positive Negative
2 Recording Start on SET Start on ALARM
3 Relay Remotely Controlled Auto switched on “Answer”
4 Star Services Not in use Active
5 Audio sequence “Live” audio on answer “Stored” audio on answer
6 C/S Not Used Active
7 Not used
8 Test Mode Off Test mode
Since the outputs available from Alarm Control Panels are varied, the AV60 can be programmed for
control by either positive or negative voltages.
The Jumper link” is used to select either pull up (to 12v) or pull down (to Gnd) Control inputs
Switch 1 Provides the option to activate the Control Inputs by applying +ve or –ve voltages.
Control Panel Outputs Switch 1 Jumper link
Switched to +12V on activation ON Pull Down
Normally +12v, removed on activation OFF
Pull Down η
Switched to 0V on activation OFF Pull Up
Normally 0V, removed on activation ON
Pull Up η η
Note : η Any unused Part Set Inputs must be linked to +12v
η η Any unused Part Set inputs must be linked to 0V
Switch 2 Selects the recording Start Time
ON Records all the time while the system is SET
OFF Starts recording only when an alarm as activated.