Access Module
The Access Module adds access control to the Advantage
®
plus system. Each Base
Module can interface and control up to seven Access Modules with each module
controlling four card readers.
General Features
Access for up to 10,000 cardholders, with 256 Access
Levels
128 programmable Time Shifts & Time Periods per
property
Optional Anti-Passback, either local or global
Programmable outputs to control equipment, such as
HVAC and lighting
Distributed Processing system with 8,000 event local
buffer memory
Optional Free Exit or Card Controlled exit
Compatible with most card types
Weigand
Proximity
Magnetic stripe
Bar Code
Level 1 (card only); Level 2 (card plus PIN) or Level 3
(card, PIN and biometrics) capability.
Dimensions
Standard UL Enclosure
17.25” W x 14.5” H x 3.25” D ( 43.82cm x 36.83cm x
8.26cm)
20 gauge cold rolled steel with lock and key
Color: Light gray w/ Advantor logo
Attack-Rated UL Enclosure
17.25” W x 14.5” H x 3.25” D ( 43.82cm x 36.83cm x
8.26cm)
18 gauge cold rolled steel with lock and key
Color: Light gray w/ Advantor logo
PCB Foot Print
12.75" W x 8.75" H (32.39cm x 22.23cm)
Alarm Points
14 programmable, supervised, hard-wired points
N/C, N/O, or Both (dry contacts)
Four programmable door inputs
10 programmable, general purpose, alarm inputs
One tamper input (alarm-on-open only)
One global free-exit input (for fire evacuation)
Programmable alarm codes
Assignable to any of eight separate arming
partitions (protected areas)
Operating Environment
0° F to 122° F (-18° C to 50° C)
Auxiliary Outputs
Six, 100mA, programmable hard-wired
One auxiliary output per controlled door (four total)
Two auxiliary outputs for general control
Optional RMOD (Relay Module)
4 RMODS per Access Module
8 relays per RMOD
Controlled by shift or user groups
Primary Power
100 to 120 VAC, 60Hz, using 16.5 VAC, 50VA, Class
2 plug-in transformer
100 to 120 VAC, 50-60Hz with enclosure mounted
transformer
200 to 240 VAC, 50-60Hz with enclosure mounted
transformer
Optional AC “Level 2” Surge Protection