User Guide

6101 Lake Ellenor Drive • Orlando, Florida 32809
Tel: 800/ADVANTOR • 407/859.3350 • Fax: 407/859.5205
http://www.advantor.com
Specifications and part numbers are subject to change without notice.
Operating Environment
0° F to 122° F (-18° C to 50° C)
Auxiliary Outputs
Four, 100mA, programmable hard-wired
Expandable to 36 total with Loop Expansion Modules
Primary Power Options
100 to 120 VAC, 60Hz, using 16.5 VAC, 50VA, Class
2 plug-in transformer
100 to 120 VAC, 50- 60Hz with internal transformer
200 to 240 VAC, 50-60Hz with internal transformer
Can utilize existing J-SIIDS Power Supply
Optional AC “Level 2” Surge Protection
Secondary Power
12VDC, 7AH, sealed lead-acid rechargeable batteries
(1 or 2, depending on kit)
Internal battery charger
Backup capabilities 12 to 24 hours typical (depending
upon installed equipment)
Integral battery supervision for AC power loss, low
battery and battery trouble
Auxiliary Power
1.6 Amps continuous at 12VDC (plug-in transformer)
1.3 Amps continuous at 12VDC (internal transformer)
1.0 Amps continuous at 12VDC (JSIIDS power
supply)
Communications
Central Station
300 Baud asynchronous, full duplex
Secure Protocol Communication
Transmit: 1070/1270 Hz/Receive: 2025/2225 Hz, FSK
Base Module RS-485 Port
Communication link: 2,000 feet maximum using
22AWG, shielded twisted pair cable
Supports a maximum of 40 RS-485 devices, to
include:
16 total keypads
8 Expansion Modules
8 SmartAudio or ListenIn Modules in any
combination
1 Wireless Module
7 Access Modules
Approvals
FCC Part 15, Class B
UL 294, “Access Control System Units” (using
optional Access Module)
UL 365, “Police Connected Burglary”
UL 609, “Local Burglary”
UL 864, “Control Units for Fire Protective Signaling
Service”
UL 985, “Household Fire Warning System Units”
UL 1023, “Household Burglar-Alarm Systems”
UL 1076, “Proprietary Burglar Alarm Units and
Systems”
UL 1610, “Central Station Burglar Alarm Units”
Communicator for UL 611, “Central Station Burglary”
CSFM (California State Fire Marshal)
ULC Commercial Fire and Burglary Pending
Part Numbers
AVR PLUS BAS Complete Base Kit, Standard
enclosure, wall-mount
transformer
AVR PLUS BAS-C Complete Base Kit, standard
enclosure, internal transformer
(120VAC), (AC “Level 2” and
telco “Level 2” dedicated line
surge protection)
AVR PLUS BAS220 Complete Base Kit, 220 VAC,
Standard enclosure, internal
transformer, (AC “Level 2” and
telco “Level 2” dedicated line
surge protection)
AVR PLUS BAS220AT Complete Base Kit, 220VAC,
Attack enclosure, internal
transformer, AC “Level 2” and
telco “Level 2 dedicated line
surge protection
AVR PLUS BAS-J JSIIDS Upgrade Kit, with AC
“Level 2” and telco “Level 2
dedicated line surge protection
AVRPLUSBASCELKT Factory integrated Base Module
and Cellular Module, assembled
in attack enclosure, with 120
VAC internal transformer.
Includes AC “Level 2” surge
protection and dial phone line
“Level 2” surge protection
AVR PLUS Complete Base Kit, Standard
enclosure with SmartAudio
module, wallmount transformer,
120VAC
90225102 PCB, Base Module, UL
40013701 Installation Connector Kit
40012810 JSIIDS Installation Connector
Kit
90237200 Standard Enclosure with Lock &
Key
90258200 Attack Enclosure with Lock and
Key
08610416 Transformer, 16.5VAC, 50VA,
Plug-In
08061699 AC “Level 2” Surge Protector
(120VAC) hardwired
08061431 AC “Level 2” Surge Protector
(220VAC) hardwired
08061698 Telco “Level 2” Dedicated Line
Surge Protector, hardwired
08060085 Telco “Level 2” Dial Line Surge
Protector, hardwired
08060084 AC “Level 2” Surge Protection
for plug-in transformer
09820450 Base Module Installation
Instructions
40003401 Enclosure Tamper Switch Kit
08061206 Battery, 12V, 7 AH, Gel Cell