19 Chapter 2 
2.5.6 RS-485 Auto Flow & RS-422 Master/Slave Modes
You can set the “Auto Flow Control” mode of RS-485 or “Master/Slave” 
mode of RS-422 by using the SW2 DIP switch for COM3~COM10. 
Please also refer to Table 2.9 for the COM port mapping with the DIP.
In RS-485, if the switch is set to “Off”, the driver automatically senses 
the direction of the data flow and switches the direction of transmission. 
No handshaking is necessary.
In RS-422, if DIP switch is set to “On,” the driver is always enabled, and 
always in high or low status. Please refer below for the default setting.
2.5.7 Redundant RS-422 Matter
In the occasion that UNO-4672 RS-422 ports need to act as multi-master 
in parallel with other RS-422 master ports. Because of the auto detection 
function, the TX port will also receive data from other RS-422 master. To 
avoid this situation in this kind of application, user can use SW5~SW12 
to turn it off, then no data will be received from TX port. Please refer to 
the Table 2.11 for the COM port mapping and refer to Figure 2.3 for the 
location. 
Table 2.10: SW2 DIP Setting 
 SW2 Status Description
ON RS-422: Master mode
RS-485: N/A
OFF(Default) RS-422: Slave mode
RS-485: Auto flow control