User manual
PCI-1241/1242 User Manual 30
Driving Capability
Maximum driving capability of each output load of each channel is 100
mA and overall maximum driving capability is 500 mA.
Connecting RELAY
When the load is a RELAY, it’s not necessary for you to connect an exter-
nal diode to absorb pulse noise because there is an instant over voltage
protection diode onboard.
Figure 3.10: Local Output Wiring Diagram
Warning: DO NOT connect the 24 V power to output
channels directly when there is no load. This
will damage the board!