D.6 Mode F waveform
Non-Retriggerable One-Shot
Mode F provides a non-retriggerable one-shot timing function. The
counter must be armed before it will function. Application of a Gate
edge to the armed counter will enable counting. When the counter
reaches TC, it will reload itself from the Load register. The counter will
then stop counting, awaiting a new Gate edge.
Note that unlike Mode C, a new ARM command is not needed after TC,
only a new Gate edge. After application of a triggering Gate edge, the
Gate input is disregard until TC.
SOURCE
COUNT
VALUE
TC OUTPUT
TC TOGGLED
OUTPUT
GATE
L-1 L-2 2 0
Mode F Waveforms
X L 1 L
56