Chapter 3 IPMI
3.3.10 Sensors and Threshold configuration
Sensor data record (SDR) repository will be stored in BMC's flash memory and can-
not be changed.
Note! UNC = Upper Non-Critical.
UC = Upper Critical
UNR = Upper Non-Recoverable
LNC = Lower Non-Critical
LC = Lower Critical
LNR = Lower Non-Recoverable
Table 3.12: Sensor List
Sensor Name Sensor
Number
Sensor
Type
Reading
Type Sensor
Logged Assertions Logged
De-assertions
Power Unit
Status
50h 09h 6Fh 00h - Power Off
04h - AC Lost
00h - Power Off
Watchdog 51h 23h 6Fh 00h - Timer Expired,
status only
01h - Hard Reset
02h - Power Down
03h - Power Cycle
N/A
Power
Failure
52h C0h 6Fh 00h - Power Failure 00h - Power Failure
07h - over 75% full
SEL Full 64h D0h 01h 09h - over 90% full
0Bh - 100% full
N/A
W83782D
Temp
00h 01 01h UNC, UNR UNC, UNR
W83782D 3.3V 01h 02h 01h LC, UC LC, UC
W83782D 2.5V 02h 02h 01h LC, UC LC, UC
W83782D 5V 03h 02h 01h LC, UC LC, UC
W83782D 12V 04h 02h 01h LC, UC LC, UC
W83782D VCC 05h 02h 01h LNC,UC LNC,UC
Note! A chassis intruder sensor is not used on the MIC-3392 platform.
Power failure sensor type "C0h" indicates a power failure event.
Apart from the following list of sensors, other sensors should be reinitial-
ized when the system is powered on or reset.
- VCC
- SEL Fullness
- System PWR monitor
- Watchdog