User manual
37 APAX-5000 I/O User Manual
Chapter 2 Analog Input
/
Output Modules
Sampling Rate: 12 samples/second (total)
CMR @ 50/60 Hz: 90 dB
NMR @ 50/60 Hz: 67 dB
Noise Suppression for Frequency: Hardware Filter (50/60 Hz)
Span Drift: ±25 ppm/° C
Zero Drift: ±6 μV/° C
Thermocouple Wire Burn-out Detection: Yes
(When the loop resistance > 1KΩ, it will detect as wire burn-out)
Input Characteristic Curve: According to IEC 61131-2
Common Mode Voltage: up to 200 VDC
Protection
Isolation: 2,500 VDC (Between channels and backplane bus)
Environment
Operating Temperature: -10 ~ 60° C (when mounted vertically)
Storage Temperature: -40 ~ 70° C
Relative Humidity: 5 ~ 95% (non-condensing)
General
Dimensions (W x H x D): 30 x 139 x 100 mm
Weight: 170 g
Power Consumption: 3.5 W @ 24 VDC (typical)