User Manual

ADAM-6200 User Manual 128
Note:
1. The value definition of DI Event Status
2. The value definition of AO Status
First register
Second register
40111 0
DI Event Status
Read
40112 1 Read
40113 2 Read
40114 3 Read
40201 0
Type Code
R/W
40202 1 R/W
40203 2 R/W
40204 3 R/W
40301 All DI Value Read
40305 0 – 15 GCL Internal Flag Value R/W
40411 0
Safety Value
R/W
40412 1 R/W
40413 2 R/W
40414 3 R/W
40401 0
Startup Value
R/W
40402 1 R/W
40403 2 R/W
40404 3 R/W
Bit Description
0 Unreliable DI value (UART Timeout)
1 Safety Value triggered
2 Startup Value triggered
Bit Description
0 Fail to provide AO Value
3 No Output Current)
9 Zero/Span Calibration Error
Bit Description
0 DI triggered to Safety Value
1 DI triggered to Startup Value
2 AO triggered to Fail Safety Value