Instructions

ADAM-6000 User Manual 36
Figure 5.5 ADAM-6051 Digital Output Wiring
5.3.3 Address Assignment
Based on the Modbus/TCP standard, the addresses of ADAM-6000 module I/O
channels you place in the system are defined by a simple rule. Please refer to
Appendix B.2.6 for information on mapping the I/O addresses. All digital inputs in the
ADAM-6051 can be configured to be used as 32-bit counters (each counter has two
addresses: a low word and a high word) by using Windows Utility (see Section 6.3).
5.4 ADAM-6052 16-ch Source-Type Isolated Digital
I/O Module
The ADAM-6052 is a high-density digital I/O module with a built-in 10/100BASE-T
interface for seamless Ethernet connectivity. The module has 8 digital inputs and 8
digital outputs. All inputs have a latch function and can be used as 3-kHz counter and
frequency input channels. The outputs support source-type and pulse output.
5.4.1 Specifications
Communication: 10/100BASE-T Ethernet
Supported protocols: MQTT, SNMP, Modbus/TCP, TCP/IP, UDP, HTTP, ICMP,
DHCP, and ARP
Supports P2P and GCL (see Section 6.7 and Chapter 8)
Digital Input
Channels: 8
Dry contact:
Logic level 0: Open
Logic level 1: Close to Ground
Wet contact:
Logic level 0: 0~3 V
DC
Logic level 1: 10~30 V
DC
Supports 3-kHz counter input (32-bit with overflow flag)
Supports 3-kHz frequency input
Supports inverted digital input status